I/O Module Error Codes
Code
(hex)
Meaning
Text
Remedy
2130
Short circuit
Short circuit
Check the wiring.
Overload of the analog
output or short circuit
2211
Overload at an input
—
2344
Overload at an output
—
Short circuit/overload of
an output
—
2345
Sensor supply overload
—
3300
Output voltage
—
Short circuit or overload
at the output
Output
3400
I/O supply voltage
failure
—
Check the I/O supply.
3412
Sensor supply not
present
—
I/O supply voltage
failure
—
3422
Actuator supply not
present
—
5112
Faulty 24 V supply
24 V supply fail
Short circuit or overload
at the 24 V supply
24V supply no x
(x = 1 or 2)
5113
Short circuit or overload
of the 5 V supply
5V supply no x
(x = 1 or 2)
5120
Cold junction invalid
Cold junction
Check the cold junction.
5160
Supply voltage faulty
Supply fail
Check the I/O supply.
6300
Parameter set faulty
Parameter set not
ok
Check the parameterization of
the specified device.
REM-11180 User Manual
|
© National Instruments
|
21