Caution

 The system shall only be used in an area of not more than

Pollution Degree 2, as defined in IEC/EN 60664-1.

Caution

 The system shall be mounted in an ATEX/IECEx-certified

enclosure with a minimum ingress protection rating of at least IP54 as

defined in IEC/EN 60079-15.

Caution

 The enclosure must have a door or cover accessible only by the

use of a tool.

Wiring the NI-9862

The NI-9862 has one 9-pin male D-Sub connector that provides connections to a

CAN bus. The NI-9862 has pins for CAN_H and CAN_L, to which you connect the CAN

bus signals. Connect these signals using twisted-pair cable.

The port has two common pins (COM) that are internally connected to the module’s

isolated reference and serve as the reference ground for CAN_H and CAN_L. You can

connect the CAN bus reference ground (sometimes referred to as CAN_V-) to one or

both COM pins. The port also has an optional shield pin, SHLD, that you can connect

to a shielded CAN cable. Connecting SHLD may improve signal integrity and EMC

performance in a noisy environment.

Caution

 You must use a UL listed ITE power supply marked LPS with the

NI-9862.

The NI-9862 requires an external power supply of +9 to +30 V to operate. Supply

power to the NI-9862 V

SUP

 pin.

Note

 Power on V

SUP

 is required for CAN operation.

The NI-9862 pinout is listed in the table below.

© National Instruments

5

NI-9862 Getting Started

Summary of Contents for NI-9862

Page 1: ...NI 9862 Getting Started 2022 07 06...

Page 2: ...Contents NI 9862 Getting Started 3 Cabling Requirements for the NI 9862 12 ni com 2 NI 9862 Getting Started...

Page 3: ...mponent in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Caution Observe all instructions and cautions in the user documentation Using the product in a man...

Page 4: ...ed location having a tool secured cover door where a minimum protection of at least IP54 is provided Special Conditions for Hazardous Locations Use in Europe and Internationally The NI 9862 has been e...

Page 5: ...isted pair cable The port has two common pins COM that are internally connected to the module s isolated reference and serve as the reference ground for CAN_H and CAN_L You can connect the CAN bus ref...

Page 6: ...A CAN bus consists of two or more CAN nodes cabled together The CAN_H and CAN_L pins of each node are connected to the main CAN bus cable through a short connection known as a stub The pair of signal...

Page 7: ...necting the NI 9862 directly to one CAN node Figure 3 Connecting the NI 9862 to a CAN Device C Series Module CAN Device Rt CAN Cable With Optional Shield SHLD CAN_H CAN_L Vsup COM Rt SHLD CAN_H CAN_L...

Page 8: ...unless otherwise noted High Speed CAN Characteristics Transceiver NXP TJA1041AT Max baud rate 1 Mbps CAN_H CAN_L bus lines voltage 27 to 40 VDC CAN Supply voltage range VSUP 9 to 30 VDC MTBF Contact...

Page 9: ...9 V DC to 30 V DC Isolation Port to earth ground Continuous 60 V DC Measurement Category I Withstand 500 V RMS verified by a 5 s dielectric withstand test Safety Compliance and Hazardous Locations St...

Page 10: ...nA IIC T4 Gc Electromagnetic Compatibility EN 61326 IEC 61326 Class A emissions Industrial immunity CE Compliance 2014 34 EU Potentially Explosive Atmospheres ATEX Product Certifications and Declarati...

Page 11: ...r more information about meeting these specifications Operating temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 70 C Storage temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 85 C Ingress protection IP4...

Page 12: ...l as other environmental information not included in this document EU and UK Customers Waste Electrical and Electronic Equipment WEEE At the end of the product life cycle all NI products must be dispo...

Page 13: ...ly with the values in the following table The onboard software selectable termination has a nominal value of 120 If you are not using the onboard termination use the values listed in the following tab...

Page 14: ...the network If all nodes meet the ISO 11898 requirements you can connect at least 30 nodes to the bus You can connect higher numbers of nodes if the nodes electrical characteristics do not degrade si...

Reviews: