and nonhazardous locations only. Follow these guidelines if you are installing the

NI-9862 in a potentially explosive environment. Not following these guidelines may

result in serious injury or death.

Caution

 Do not disconnect I/O-side wires or connectors unless power has

been switched off or the area is known to be nonhazardous.

Caution

 Do not remove modules unless power has been switched off or

the area is known to be nonhazardous.

Caution

 Substitution of components may impair suitability for Class I,

Division 2, or Zone 2.

Caution

 The system must be installed in an enclosure certified for the

intended hazardous (classified) location, having a tool secured cover/door,

where a minimum protection of at least IP54 is provided.

Special Conditions for Hazardous Locations Use in Europe and

Internationally

The NI-9862 has been evaluated as Ex nA IIC T4 Gc equipment under

DEMKO 07ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI-9862 is

marked   II 3G and is suitable for use in Zone 2 hazardous locations, in ambient

temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI-9862 in Gas Group

IIC hazardous locations, you must use the device in an NI chassis that has been

evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.

Caution

 Transient protection shall be provided that is set at a level not

exceeding 140% of the peak rated voltage value of 85 V at the supply

terminals to the equipment.

ni.com

4

NI-9862 Getting Started

Summary of Contents for NI-9862

Page 1: ...NI 9862 Getting Started 2022 07 06...

Page 2: ...Contents NI 9862 Getting Started 3 Cabling Requirements for the NI 9862 12 ni com 2 NI 9862 Getting Started...

Page 3: ...mponent in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Caution Observe all instructions and cautions in the user documentation Using the product in a man...

Page 4: ...ed location having a tool secured cover door where a minimum protection of at least IP54 is provided Special Conditions for Hazardous Locations Use in Europe and Internationally The NI 9862 has been e...

Page 5: ...isted pair cable The port has two common pins COM that are internally connected to the module s isolated reference and serve as the reference ground for CAN_H and CAN_L You can connect the CAN bus ref...

Page 6: ...A CAN bus consists of two or more CAN nodes cabled together The CAN_H and CAN_L pins of each node are connected to the main CAN bus cable through a short connection known as a stub The pair of signal...

Page 7: ...necting the NI 9862 directly to one CAN node Figure 3 Connecting the NI 9862 to a CAN Device C Series Module CAN Device Rt CAN Cable With Optional Shield SHLD CAN_H CAN_L Vsup COM Rt SHLD CAN_H CAN_L...

Page 8: ...unless otherwise noted High Speed CAN Characteristics Transceiver NXP TJA1041AT Max baud rate 1 Mbps CAN_H CAN_L bus lines voltage 27 to 40 VDC CAN Supply voltage range VSUP 9 to 30 VDC MTBF Contact...

Page 9: ...9 V DC to 30 V DC Isolation Port to earth ground Continuous 60 V DC Measurement Category I Withstand 500 V RMS verified by a 5 s dielectric withstand test Safety Compliance and Hazardous Locations St...

Page 10: ...nA IIC T4 Gc Electromagnetic Compatibility EN 61326 IEC 61326 Class A emissions Industrial immunity CE Compliance 2014 34 EU Potentially Explosive Atmospheres ATEX Product Certifications and Declarati...

Page 11: ...r more information about meeting these specifications Operating temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 70 C Storage temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 85 C Ingress protection IP4...

Page 12: ...l as other environmental information not included in this document EU and UK Customers Waste Electrical and Electronic Equipment WEEE At the end of the product life cycle all NI products must be dispo...

Page 13: ...ly with the values in the following table The onboard software selectable termination has a nominal value of 120 If you are not using the onboard termination use the values listed in the following tab...

Page 14: ...the network If all nodes meet the ISO 11898 requirements you can connect at least 30 nodes to the bus You can connect higher numbers of nodes if the nodes electrical characteristics do not degrade si...

Reviews: