background image

FP-AI-102 and cFP-AI-102

8

ni.com

backplane PE ground terminal to the system safety ground 
using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. 
panhead screw shipped with the backplane to secure the ring 
lug to the backplane PE ground terminal.

As with any hazardous voltage wiring, make sure that all 
wiring and connections meet applicable electrical codes and 
commonsense practices. Mount terminal bases and backplanes 
in an area, position, or cabinet that prevents accidental or 
unauthorized access to wiring that carries hazardous voltages.

The isolation of the [c]FP-AI-102 is certified as 
double-insulated for working voltages of 250 V

rms

. Do 

not

 use 

the [c]FP-AI-102 as the only isolating barrier between human 
contact and working voltages of more than 250 V

rms

.

Operate the [c]FP-AI-102 only at or below Pollution Degree 2. 
Pollution Degree 2 means that only nonconductive pollution 
occurs in most cases. Occasionally, however, a temporary 
conductivity caused by condensation must be expected.

Do 

not

 operate FieldPoint products in an explosive atmosphere 

or where there may be flammable gases or fumes. If you need 
to operate FieldPoint products in such an environment, the 
FieldPoint products 

must

 be in a suitably rated enclosure.

Operate the [c]FP-AI-102 at or below Installation Category II. 
Installation Category II is for measurements performed on 
circuits directly connected to the electrical distribution system. 
This category refers to local-level distribution, such as that 
provided by a standard wall outlet.

Specifications

The following specifications are typical for the range –40 to 70 °C 
unless otherwise noted. Gain error is calculated as a percentage of 
input.

Input Characteristics

Number of channels.......................... 8

ADC resolution................................. 12 bits

Type of ADC..................................... Successive approximation

Update rate (all channels) ................. 360 Hz (2.8 ms)

Summary of Contents for FP-AI-102

Page 1: ...l Instruments FP AI 102 Manual Get Pricing Availability at ApexWaves com Call Today 1 800 915 6216 Email sales apexwaves com https www apexwaves com modular systems national instruments fieldpoint FP...

Page 2: ...referred to inclusively as the c FP AI 102 For information about configuring and accessing the c FP AI 102 over a network refer to the user manual for the FieldPoint network module you are using Feat...

Page 3: ...cFP BP x Hot plug and play enables you to install the cFP AI 102 onto a powered backplane without disturbing the operation of other modules or connector blocks The cFP AI 102 receives operating power...

Page 4: ...nd for an external supply to power field devices The cFP CB x connector blocks provide the same connections for the cFP AI 102 Table 1 lists the terminal assignments for the signals associated with ea...

Page 5: ...or connector block Field devices source power from the Vsup and COM terminals Refer to the following section for detailed wiring diagrams Caution Cascading power between two modules defeats isolation...

Page 6: ...2 Analog Input Circuit One Channel The input ranges for voltage signals are 0 20 0 60 0 120 20 60 and 120 V Connect the positive lead of a voltage source to the Vin terminal and the negative lead to t...

Page 7: ...odule of its presence When the network module recognizes the c FP AI 102 it sends initial configuration information to the c FP AI 102 After the c FP AI 102 receives this initial information the green...

Page 8: ...ts that can be at hazardous potentials under normal conditions unless the product is specifically designed for such an application as is the c FP AI 102 Even though the c FP AI 102 is designed to hand...

Page 9: ...ow Pollution Degree 2 Pollution Degree 2 means that only nonconductive pollution occurs in most cases Occasionally however a temporary conductivity caused by condensation must be expected Do not opera...

Page 10: ...102 115 g 4 0 oz Power Requirements Power from network module 400 mW Isolation Voltage Maximum isolation voltage 250 Vrms Installation Category II Channel to channel isolation No isolation between cha...

Page 11: ...3 ms half sine 3 shocks 30 g 11 ms half sine 3 shocks Operating vibration random IEC 60068 2 34 FP AI 102 10 500 Hz 2 2 grms cFP AI 102 10 500 Hz 5 grms Operating vibration sinusoidal IEC 60068 2 6 c...

Page 12: ...tion of Conformity DoC for this product for any additional regulatory compliance information To obtain the DoC for this product click Declaration of Conformity at ni com hardref nsf Mechanical Dimensi...

Page 13: ...6 Austria 0662 45 79 90 0 Belgium 02 757 00 20 Brazil 55 11 3262 3599 Canada Calgary 403 274 9391 Canada Montreal 514 288 5722 Canada Ottawa 613 233 5949 Canada Qu bec 514 694 8521 Canada Toronto 905...

Reviews: