cFP-RLY-425
8
ni.com
Insert the connector into the cFP-RLY-425 as shown in Figure 8,
then tighten both flange screws on the connector.
Figure 8.
Installing One Assembled Screw-Terminal Connector
Connecting Loads to the cFP-RLY-425
Wire a load to a channel of the cFP-RLY-425 as shown in Figure 9.
Install a 5 A, 250 V maximum, fast-acting fuse (F 5 A L 250V) at
the COM
x
terminal to protect the module and the load from
damage.
Figure 9.
Connecting a Load to One Channel of the cFP-RLY-425