Chapter 4
Analog Input
X Series User Manual
4-22
ni.com
Using Differential Connections for
Ground-Referenced Signal Sources
Fig
u
re 4-10 shows how to connect a gro
u
nd-referenced signal so
u
rce to the
MIO X Series device config
u
red in differential mode.
Figure 4-10.
Differential Connections for Ground-Referenced Signal Sources
With this type of connection, the NI-PGIA rejects both the common-mode
noise in the signal and the gro
u
nd potential difference between the signal
so
u
rce and the device gro
u
nd, shown as V
cm
in the fig
u
re.
AI+ and AI– m
u
st both remain within ±11 V of AI GND.