Special Conditions for Hazardous Locations Use in Europe and
Internationally

The cRIO-9037 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO 12
ATEX 1202658X and is IECEx UL 14.0089X certified. Each device is marked   II 3G and is
suitable for use in Zone 2 hazardous locations, in ambient temperatures of -20 °C ≤ Ta ≤
55 °C.

Caution

 

Transient protection shall be provided that is set at a level not exceeding

140% of the peak rated voltage value of 85 V at the supply terminals to the
equipment.

Caution

 

The system shall only be used in an area of not more than Pollution

Degree 2, as defined in IEC/EN 60664-1.

Caution

 

The system shall be mounted in an ATEX/IECEx-certified enclosure with

a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15.

Caution

 

The enclosure must have a door or cover accessible only by the use of a

tool.

Electromagnetic Compatibility Guidelines

This product was tested and complies with the regulatory requirements and limits for
electromagnetic compatibility (EMC) stated in the product specifications. These requirements
and limits provide reasonable protection against harmful interference when the product is
operated in the intended operational electromagnetic environment.

This product is intended for use in industrial locations. However, harmful interference may
occur in some installations, when the product is connected to a peripheral device or test object,
or if the product is used in residential or commercial areas. To minimize interference with
radio and television reception and prevent unacceptable performance degradation, install and
use this product in strict accordance with the instructions in the product documentation.

Furthermore, any changes or modifications to the product not expressly approved by National
Instruments could void your authority to operate it under your local regulatory rules.

Caution

 

To ensure the specified EMC performance, operate this product only with

shielded cables and accessories. The DC power input cables may be unshielded.

Caution

 

To ensure the specified EMC performance, you must use an isolated cable

with the RS-485 serial port, such as NI part number 184428-01.

Caution

 

To ensure the specified EMC performance, the length of any cable

connected to the video and V2 ports must be no longer than 3 m (10 ft). The length
of any cable connected to the RS-232 and RS-485 ports must be no longer than

NI cRIO-9037 Getting Started Guide

  | 

© National Instruments

  | 

3

Summary of Contents for cRIO-9037

Page 1: ...GETTING STARTED GUIDE NI cRIO 9037 Embedded CompactRIO Controller with Real Time Processor and Reconfigurable FPGA This document describes how to begin using the National Instruments cRIO 9037...

Page 2: ...n switched off or the area is known to be nonhazardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of components may i...

Page 3: ...rmful interference when the product is operated in the intended operational electromagnetic environment This product is intended for use in industrial locations However harmful interference may occur...

Page 4: ...for a product visit ni com certification and search for the LR certificate or look for the Lloyd s Register mark on the product Caution In order to meet the EMC requirements for marine applications in...

Page 5: ...e Caution Never touch the exposed pins of connectors Note Do not install a device if it appears damaged in any way 3 Unpack any other items and documentation from the kit Store the device in the antis...

Page 6: ...tion visit ni com info and enter the Info Code swsupport Installing C Series Modules Complete the following steps to install a C Series module 3 2 2 1 1 Verify that power is not connected to the I O c...

Page 7: ...e cRIO 9037 can be powered on when you remove modules Installing the Antennas Complete the following steps to install the antennas on the cRIO 9037 Note NI recommends connecting both antennas for opti...

Page 8: ...Cable Retention Mounts 13 USB Device Port 14 Power and Reset Buttons Connecting the cRIO 9037 to Ground You must connect the cRIO 9037 grounding terminal to the grounding electrode system of the facil...

Page 9: ...ilters and regulates the supplied power and provides power for the C Series modules The cRIO 9037 has a primary power input V1 and a secondary power input V2 The POWER LED on the cRIO 9037 indicates w...

Page 10: ...d positive leads of the power supply as shown in the following figure Figure 3 Installing a Ferrite on the Power Leads 2 1 1 Pass the leads through the ferrite twice leaving 50 mm to 75 mm 2 in to 3 i...

Page 11: ...econdary power supply Powering On the cRIO 9037 When you power on the cRIO 9037 for the first time the device boots into safe mode The POWER LED illuminates the STATUS LED illuminates briefly and then...

Page 12: ...pecifications on ni com manuals for shock and vibration specifications The device driver software automatically detects the cRIO 9037 If the device driver software does not detect the cRIO 9037 verify...

Page 13: ...the password field blank 6 Click OK 7 Click Change Password 8 Enter and re enter a new password 9 Click OK 10 Click Save 11 Click OK to confirm you are changing the password Caution NI cannot recover...

Page 14: ...RIO 9037 1856AAA 4 Click the Network Settings tab 5 Select your country 6 Select Connect to a wireless network as the Wireless Mode You may need to upload a certificate by clicking Certificate Managem...

Page 15: ...under Remote Systems 3 Select the Network Settings tab to configure the IP and other network settings 4 Optional Use the RJ 45 Ethernet port 1 to reconnect the cRIO 9037 to the host computer The cRIO...

Page 16: ...uccessful and appropriate for your application skip to Step 6 4 In MAX expand your system under Remote Systems 5 Select the Network Settings tab to configure the IP and other network settings 6 Reboot...

Page 17: ...r 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Console Out enabled Network settings reset RT Startup App disabled FPGA Startup App disabled Console Out enabled RT Startu...

Page 18: ...ling safe mode in MAX Refer to the Measurement Automation Explorer MAX Help for information about safe mode Blinks four times and pauses The cRIO 9037 is in safe mode The software has crashed twice wi...

Page 19: ...ICATION SUPPORT Services NI Community NI CompactRIO Developer s Guide Software Support ni com info swsupport Support ni com support SOFTWARE NI cRIO 9037 Specifications Configuring a Project ni com ma...

Page 20: ...ne support outside the United States visit the Worldwide Offices section of ni com niglobal to access the branch office websites which provide up to date contact information support phone numbers emai...

Reviews: