Digital Input/Output and PFI
Using a Digital Source
To use DI Reference Trigger with a digital source, specify a source and a rising or falling edge.
Either PFI or one of several internal signals on the cDAQ chassis can provide the source. Refer
to the
Device Routing in MAX
topic in the
NI-DAQmx Help
or the
LabVIEW Help
for more
information.
Using an Analog Source
Some C Series modules can generate a trigger based on an analog signal. In NI-DAQmx, this is
called the Analog Comparison Event.
When you use an analog trigger source, the acquisition stops on the first rising or falling edge of
the Analog Comparison Event signal, depending on the trigger properties.
Note
Depending on the C Series module capabilities, you may need two modules
to utilize analog triggering.
Routing DI Reference Trigger Signal to an Output Terminal
You can route DI Reference Trigger to any output PFI terminal. Reference Trigger is active high
by default.
DI Pause Trigger Signal
You can use the DI Pause Trigger (di/PauseTrigger) signal to pause and resume a measurement
acquisition. The internal sample clock pauses while the external trigger signal is active and
resumes when the signal is inactive. You can program the active level of the pause trigger to be
high or low.
Using a Digital Source
To use DI Pause Trigger, specify a source and a polarity. The source can be either from PFI or
one of several other internal signals on your cDAQ chassis. Refer to the
Device Routing in MAX
topic in the
NI-DAQmx Help
or the
LabVIEW Help
for more information.
Using an Analog Source
Some C Series modules can generate a trigger based on an analog signal. In NI-DAQmx, this is
called the Analog Comparison Event.
When you use an analog trigger source, the internal sample clock pauses when the Analog
Comparison Event signal is low and resumes when the signal goes high (or vice versa).
Note
Depending on the C Series module capabilities, you may need two modules
to utilize analog triggering.
Note
Pause triggers are only sensitive to the level of the source, not the edge.