Chapter 3
Feature Descriptions
©
National Instruments Corporation
3-3
cFP-21xx and cFP-BP-x User Manual
Table 3-1 shows how modules are configured after hot swapping.
LED Indicators
The cFP-21
xx
has several LEDs to indicate status information.
POWER LED
The green
POWER
LED is lit while the cFP-21
xx
is powered on.
This LED indicates that the power supply connected to the cFP-21
xx
is
acceptable, and that the cFP-21
xx
is supplying power to the I/O modules.
STATUS LED
The red
STATUS
LED is off in normal operation mode. The cFP-21
xx
indicates specific error conditions by flashing
STATUS
a specific number
of times. Refer to the
section of
Appendix A,
, for more information about
STATUS
LED error indications.
LINK ACT LED
The yellow
LINK
ACT
LED blinks when the cFP-21
xx
receives data from
or transmits data to the Ethernet. Unrelated network activity causes this
LED to blink occasionally even when the cFP-21
xx
is inactive.
Table 3-1.
Module Configuration Results After Hot Swapping
Replacement
Module
Factory Configuration
Checked?
1
Replacement Module
Configuration after Hot Swapping
Compatible with the removed
module
Yes or No
Same as the removed module
Incompatible with the removed
module but compatible with the
stored configuration
No
Same as the stored configuration
Yes
Factory default configuration
Incompatible with the removed
module and incompatible with
the stored configuration
Yes or No
Factory default configuration
1