background image

19

W415-0612 / C / 01.25.08

CAULKING

#10x2"

SCREWS

HIGH

TEMPERATURE

SEALANT

#8 x 1/2"

SCREWS

7" RIGID
VENT PIPE

2" OVERLAP

4" RIGID
VENT PIPE

ATTE

NTION-CH

AUD

CAUTI

ON - H

OT

FIGURE 29

1. 

Move the 

fi

 replace into position. Measure the vent length required 

between terminal and 

fi

 replace taking into account the additional length 

needed for the 

fi

 nished wall surface and any 1¼" overlaps between vent-

ing components.

2. 

Apply high temperature sealant W573-0007 (not supplied) to the outer 

edge of the 4" inner collar of the 

fi

 replace.  Attach the 

fi

 rst 4" rigid vent pipe 

component and secure using 3 self tapping screws. Repeat using the 7" 
rigid vent pipe component. 

NOTE: Before attaching elbows to the collars on the back of the 

fi

 replace, 1 1/2" will need to be trimmed off the 4" collar.

3. 

Holding the air terminal (lettering in an upright, readable position), insert into 

both vent pipes with a twisting motion to ensure that both the terminal sleeves engage 
into the vent pipes and the sealant. Secure the terminal to the exterior wall and make weather tight by sealing with 
caulking (not supplied). 

 

The air terminal mounting plate may be recessed into the exterior wall or siding by 1½", the depth of the return 

fl

 ange.

STORM 

COLLAR

FLASHING

CAULKING

WEATHER

    SEALANT

2”

AIR INLET
BASE

FIGURE 27

1. 

Install the 4" 

fl

 exible vent pipe to the 

fi

 replace. Secure with 3 screws and 

fl

 at washers. Seal the joint and screw holes using the high temperature sealant  

W573-0007 (not supplied). 

2. 

Install the 7" 

fl

 exible vent pipe to the 

fi

 replace. Attach and seal the joints 

using the high temperature sealant W573-0002 (not supplied).

FIREPLACE VENT CONNECTION

FIGURE 28

2” OVERLAP

HIGH TEMPERATURE
SEALANT

#8 X 1/2”

SELF

DRILLING

SCREWS

4.

  Thread the air terminal connector / vent pipe assembly down through the roof. The air 

terminal must be located vertically and plumb.  Attach the air terminal connector to the roof 
support, ensuring that the top of the air terminal is 16” above the highest point that it penetrates 
the roof.  Figure 27.  

DO NOT CLAMP THE FLEXIBLE VENT PIPE.

5. 

Remove nails from the shingles, above and to the sides of the chimney. Place the 

fl

 ashing 

over the air terminal connector leaving a min. 3/4” of the air terminal connector showing 
above the top of the 

fl

 ashing.  Slide the 

fl

 ashing underneath the sides and upper edge of 

the shingles. Ensure that the air terminal connector is properly centred within the 

fl

 ashing, 

giving a 3/4” margin all around. Fasten to the roof. Do 
not nail through the lower portion of the 

fl

 ashing. Make 

weather-tight by sealing with caulking. Where possible, 
cover the sides and top edges of the 

fl

 ashing with roo

fi

 ng 

material.  Figure 27.

6.

  Aligning the seams of the terminal and air terminal 

connector, place the terminal over the air terminal 
connector making sure the vent pipe goes into the hole in the terminal.  Secure with 
the three screws provided.  Figure 27.

7.

 Apply a heavy bead of weatherproof caulking 2" above the 

fl

 ashing.  Note:  Maintain 

a minimum 2” space between the air inlet base and the storm collar.  Install the storm 
collar around the air terminal and slide down to the caulking. Tighten to ensure that a 
weather-tight seal between the air terminal and the collar is achieved.  Figure 27.

8. 

If more vent pipe needs to be used to reach the 

fi

 replace, couple them together 

as illustrated

.

 The vent system must be supported approximately every 3 feet for both 

vertical and horizontal runs. Use noncombustible strapping to maintain the minimum 
1" clearance to combustibles.  Figure 24.

4” FLEXIBLE

VENT PIPE

7” FLEXIBLE 

VENT PIPE

INNER

PIPE

HIGH

TEMPERATURE

SEALANT

AIR

TERMINAL

CONNECTOR

FIGURE 26

USING RIGID VENT COMPONENTS

The vent system must be supported approximately every 3 feet for both vertical and horizontal runs.  Use Wolf Steel vent 
spacers

 

W615-0033

 every 3 feet on either side of each elbow to maintain the minimum 1¼" clearance between the 7" rigid 

vent pipe and 4" rigid vent pipes. Use Napoleon® support ring assembly 

W010-0370

 or equivalent noncombustible strapping 

to maintain the minimum clearance to combustibles for both vertical and horizontal runs. 

HORIZONTAL AIR TERMINAL INSTALLATION

Summary of Contents for Vittoria GD19N

Page 1: ...s supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified inst...

Page 2: ...nder water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed or qualified service person Do not strike or slam shut the f...

Page 3: ...ents used in the installation of the fireplace NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life subject to the following condi tions During the first...

Page 4: ...log A carbon monoxide detector is required in all rooms containing gas fired appliances The appliance off valve must be a T handle gas cock The flexible connector must not be longer than 36 inches Th...

Page 5: ...RTV this same sleant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the fireplace flue colla...

Page 6: ...ns use either the 5 foot Vent Kit GD220 or the 10 foot Vent Kit GD330 The maximum allowable vertical vent length is 35 feet the minimum is 3 feet For optimum flame appearance and fireplace performance...

Page 7: ...of horizontal run in addition to the 45 offset In this case zero rise is acceptable when using rigid See FIGURE 5a Flexible venting must maintain a 6 rise See FIGURE 5b TYPICAL VENT INSTALLATIONS PER...

Page 8: ...8 W415 0612 C 01 25 08 FIGURE 6 MINIMUM AIR TERMINAL LOCATION CLEARANCES...

Page 9: ...u m of 35 feet Vertical rise is equal to or greater t h a n t h e horizontal run Horizontal run verti cal rise to m a x i m u m of 35 feet Vertical rise is equal to or greater t h a n t h e horizontal...

Page 10: ...n is acceptable FIGURE 8 The shaded area within the lines represents acceptable values for HT and VT For the following symbols used in the venting calculations and examples are greater than equal to o...

Page 11: ...ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft HT HR HO 5 5 8 1 13 6 ft HT VT 13 6 5 5 19 1 ft Formula 1 HT 4 2 VT 4 2 VT 4 2 x 5 5 23 1...

Page 12: ...RIZONTAL TERMINATION Simple venting configuration only two 90 elbows FIGURE 13 H3 90 90 90 V2 H1 V1 H2 V1 9 ft V2 6 ft VT V1 V2 9 6 15 ft H1 3 ft H2 2 ft H3 1 5 ft HR H1 H2 H3 3 2 1 5 6 5 ft HO 03 fou...

Page 13: ...mula 2 HT VT 24 75 feet 20 45 24 75 Since both formulas are met this vent configuration is acceptable FIGURE 15 For vent configurations requiring more than two 90 elbows the following formulas apply F...

Page 14: ...Since both formulas are met this vent configuration is acceptable FIGURE 16 For vent configurations requiring more than zero 90 elbow top exit or one 90 elbow rear exit the following formulas apply F...

Page 15: ...ormula 2 HT VT 35 feet 20 6 35 Since only formula 2 is met this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formul...

Page 16: ...exit remove the components as illustrated When reinstalling in the alternate position Check gaskets for tears replace if necessary to ensure a proper seal TOP EXIT CONVERSION FIGURE 18 4 Collar 4 Gask...

Page 17: ...Dura Vent Selkirk Direct Temp American Metal Amerivent or Wolf Steel rigid or flexible vent components For safe and proper operation of the fireplace follow the venting instructions exactly CAULKING V...

Page 18: ...f the high temperature sealant W573 0007 not supplied NOTE If using pipe clamps to connect vent components 3 screws must also be used to ensure the connection cannot slip off 2 Using the 7 flexible ve...

Page 19: ...t that it penetrates the roof Figure 27 DO NOT CLAMP THE FLEXIBLE VENT PIPE 5 Remove nails from the shingles above and to the sides of the chimney Place the flashing over the air terminal connector le...

Page 20: ...slide down to the caulking Tighten to ensure that a weather tight seal between the air terminal and the collar is achieved 9 Continue adding rigid vent pipe sections sealing and securing as above Att...

Page 21: ...he mobile home appliance This appliance is certified to be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This fireplace is only for use w...

Page 22: ...Combustible Finishing 0 to rear 0 to front face top and sides 13 recessed depth Rear Vent 39 1 8 to enclosure top from base of the unit 45 1 8 to ceiling from base of the unit Top Vent 53 1 8 to encl...

Page 23: ...CK COMBUSTIBLE NON COMBUSTIBLE 26 3 8 MINIMUM PLUS RISE 0 IF NON COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE The fireplace requires a minimum enclosure height of 53 1 8 for a top vent and 39...

Page 24: ...heavy use care when lifting and ensure they are firmly secured once installed This front facing does not replace the main glass door Do not operate without the main glass door installed The front fac...

Page 25: ...LIFIED INSTALLER and must be connected and grounded in accordance with local codes In the absence of local codes use the current CSA C22 1 CANADIAN ELECTRICAL CODE in Canada or the current ANSI NFPA 7...

Page 26: ...htly and lift out of bottom retainer FIGURE 58 90 2 Place the left log as shown ensuring the hole on the underside is placed onto the burner pin This will rest on the left side of the rear log 1 Place...

Page 27: ...able from your Napoleon dealer CHARCOAL EMBERS LOGO PLACEMENT GLOWING EMBERS VERMICULITE Remove the backing of the logo supplied and place on the glass viewing door as indicated FIGURE 61 CONTROL FUNC...

Page 28: ...o the two corresponding spade connectors on the back of the on off switch for the burner located behind the lower access panel Repeat connecting the wires to the Night LightTM on off switch for remote...

Page 29: ...ETY READ BEFORE OPERATING OPERATION MAINTENANCE MAINTENANCE TURN OFF THE GAS AND UNPLUG ELECTRICAL POWER BEFORE SERVICING THE STOVE Caution Label all wires prior to disconnection when servicing contro...

Page 30: ...TMENTS PILOT INJECTOR AND ORIFICE REPLACEMENT VENTURI ADJUSTMENT Remove the 2 screws securing the burner Natural gas models have air shutters set to 0 031 open 1 32 Propane models have air shutters se...

Page 31: ...R SLEEVE 22 W010 0567 ROOF SUPPORT 23 W170 0063 STORM COLLAR 24 W263 0055 ROOF FLASHING GD112 FLAT ROOF 20 W670 0006 AIR TERMINAL 21 W490 0073 4 7 INNER OUTER SLEEVE 22 W010 0567 ROOF SUPPORT 23 W170...

Page 32: ...32 W415 0612 C 01 25 08 25 29 6 7 27 5 12 1 2 3 21 8 18 24 21 20 23 22 17 31 4 32...

Page 33: ...ire about 3 16 away from the I terminal on the module If no spark the I terminal module must be replaced If there is a spark the I terminal is fine Inspect pilot assembly for a shorted wire or cracked...

Page 34: ...cted in the right order Module or Valve Conduct the following test to verify if the problem is the module or valve To measure voltages turn multimeter to DC place the red lead from multimeter on the s...

Page 35: ...35 W415 0612 C 01 25 08 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Page 36: ...36 W415 0612 C 01 25 08 NOTES...

Reviews: