3.0 FURNACE SIZING
TABLE 1 - RANGE OF TEMPERATURE RISE
Furnace Models
Temperature Rise
ALL
High Fire (HF) 35 - 65°F (20 - 36°C)
Low Fire (LF) 20 - 50°F (11 - 28°C)
H12.15.4
H7.0.4
The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures
described in the manuals of the
Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI)
, or
by any other method which is suitable for local conditions, provided the results obtained are in substantial
agreement with, and not less than those obtained using the procedure described in their manuals.
In the United States,
“Manual J - Load Calculation,”
published by the Air Conditioning Contractors of America,
describes a suitable procedure for calculating the maximum hourly heat loss.
If the installation is a retro
fi
t application, do not rely on the capacity of the existing heating equipment as a
method to size the new furnace. Many of the heat transfer multiples listed in earlier versions of load calculation
manuals were much higher than those listed in more recent editions. It is possible that energy saving
measures have been completed since the installation of the existing furnace. This might include additional
insulation in the attic or walls, the application of sprayed foam insulation, the addition of storm windows and
doors, weather-stripping, caulking, etc.
Many of the older furnaces were equipped with large belt drive blower systems, operating at low RPM’s. If
replacing an existing furnace, be sure that the existing ductwork can handle the amount of air
fl
ow necessary
for a reasonable temperature rise. Most older gas furnaces operated with a system temperature rise of 70
- 100°F (39 - 56°C). This furnace is designed to be operated with a system temperature rise (
∆
T) of High
NOTE:
The return air system is equally as important as the supply air system. An under-sized return air system
will prevent suf
fi
cient quantities of air from reaching the supply air system and will consequently reduce the
service life of the furnace and its components.
Fire 35 - 65°F (20 - 36°C), Low Fire 20 - 50°F (11 - 28°C). If
the furnace selected has an identical output capacity as the
original furnace, a substantial increase in system air
fl
ow will
be necessary. See Table 1 and the air
fl
ow characteristics in
Section 18 of this manual,
“Airfl ow”.
Existing ductwork should be assessed for its air handling
capabilities.
The
“Equal Friction Chart,”
as published by ASHRAE and
HRAI, is the basis for the various air duct calculators available
through heating supply companies. Following the air velocity
guide lines, according to the
“Equal Friction Chart,”
or a slide
rule air duct calculator, a typical 6” round duct has a capacity of
approximately 100 cfm.
Summary of Contents for ULTIMATE 9700 Series
Page 27: ...W415 1243 E 11 27 17 27 IOM FIGURE 14A DIRECT VENT TERMINAL CLEARANCES...
Page 28: ...W415 1243 E 11 27 17 28 IOM IOM FIGURE 14B NON DIRECT VENT TERMINAL CLEARANCES...
Page 58: ...W415 1243 E 11 27 17 58 IOM IOM 23 0 SERVICE HISTORY 43 1...
Page 74: ...6 0 NOTES 44 1 W415 1243 E 11 27 17 UM 74...