W415-0619 / B / 03.03.08

THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER 

 to conform with local 

codes. Installation practices vary from region to region and  it is important to know the speci

fi

 cs that apply to your area, for 

example: in Massachusetts State:

•   The 

fi

 replace damper must be removed or welded in the open position prior to installation of a 

fi

 replace insert or gas log.

•   A carbon monoxide detector is required in all rooms containing gas 

fi

 red appliances.

•   The appliance off valve must be a “T” handle gas cock.
•   The 

fl

 exible connector must not be longer than 36 inches.

•   The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
•   WARNING: This product must be installed by a licensed plumber or gas 

fi

 tter when installed in the Commonwealth of Massachusetts.

In absence of local codes, install to the current CAN/CGA -B149 Installation Code in Canada or to the National Fuel Gas 
Code, ANSI Z223.1, and NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with 
the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or ANSI Z223.1 and NFPA 54 
in the United States.
The 

fi

 replace and its individual shutoff valve must be disconnected from 

the gas supply piping system during any pressure testing of that system 
at test pressures in excess of 1/2 psig (3.5 kPa). The 

fi

 replace  must 

be isolated from the gas supply piping system by closing its individual 
manual shutoff valve during any pressure testing of the gas supply piping  
system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the 

fi

 replace is installed directly on carpeting, vinyl tile or other 

combustible material other than wood 

fl

 ooring,  the 

fi

 replace shall be 

installed on a metal or wood panel extending the full width and depth.

GENERAL INSTRUCTIONS

GENERAL INFORMATION

FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!

 

 

* When the 

fi

 replace is installed at elevations above 4,500ft,  and in the absence of speci

fi

 c recommendations from 

the local authority having jurisdiction, the certi

fi

 ed high altitude input rating shall be reduced at the rate of 4% for 

each additional 1,000ft. 

This 

fi

 replace is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home 

installation. 
The natural gas model can only be installed  in a mobile home that is permanently positioned on its site and fueled with 
natural gas.

This 

fi

 replace may be installed in an aftermarket permanently located, manufactured (mobile) home, where not 

prohibited by local codes.
This 

fi

 replace is only for use with the type of gas indicated on the rating plate. This 

fi

 replace is not convertible for 

use with other gases, unless a certi

fi

 ed kit is used.

Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
Purge all gas lines with the glass door of the 

fi

 replace open.  Assure that a continuous gas 

fl

 ow is at the burner 

before closing the door.

Objects placed in front of the 

fi

 replace must be kept a minimum of 48” from the front face of the unit. 

Use only Napoleon® accessories designed for and listed with the model.

RATES AND EFFICIENCIES

NATURAL GAS

PROPANE GAS

Altitude

0 - 4,500*

0 - 4,500*

Maximum Input

6,000

6,000

Maximum Output

4,680

4,680

Ef

fi

 ciency

78%

78%

Minimum Inlet Gas Suppy Pressure

4.5” Water Column

11” Water Column

Maximum Inlet Gas Supply Pressure

7” Water Column

13” Water Column

Manifold Pressure Under Flow Conditions

3.5” Water Column

10” Water Column

Summary of Contents for TORCH GT8P

Page 1: ...y appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot re...

Page 2: ...erials gasoline and other flammable vapours and liquids Under no circumstances should this fireplace be modified This fireplace must not be connected to a chimney flue pipe serving a separate solid fu...

Page 3: ...ents and wearable parts such as blowers gas valves thermal switch switches wiring remote controls ignitor gasketing and pilot assembly are covered and NAPOLEON will provide replacement parts free of c...

Page 4: ...on carpeting vinyl tile or other combustible material other than wood flooring the fireplace shall be installed on a metal or wood panel extending the full width and depth GENERAL INSTRUCTIONS GENERA...

Page 5: ...als on the inner exhaust flue only the outer air intake joints must be sealed using a red high temperature silicone RTV This same sealant may be used on both the inner exhaust and outer intake vent pi...

Page 6: ...ated with the insulation wrapped in a protective sleeve to minimize condensation Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed Use firesto...

Page 7: ...24 2a Horizontal run if vent run includes vertical rise 4 7 FT 2b Vertical run Immediately off the fireplace if 7 FT maximum horizontal run is required 18 7 FT 2b 2c FIGURE 2a 4 MIN 24 MAX 8 18 MAXIMU...

Page 8: ...excluding fireplace and air terminal connections N A 2 Rise per foot recommended 1 4 N A Rise per foot allowable 0 N A Vertical run when not venting horizontally 24 19 1 2 FT 3a 3c Horizontal run 4 5...

Page 9: ...9 W415 0619 B 03 03 08 O O B B G A F C H H L K J M MINIMUM AIR TERNMINAL LOCATION CLEARANCES N D E O FIGURE 4...

Page 10: ...g to cut them Use a plumb bob to line up the center of the openings Do not fill this space with any type of material A vent pipe shield will prevent any materials such as insulation from filling up th...

Page 11: ...e joints may be sealed using high temperature sealant W573 0002 not supplied or the high temperature sealant W573 0007 Mill Pac not supplied However the high temperature sealant W573 0007 Mill Pac not...

Page 12: ...ed Conversion Kits The mobile home appliance is field convertible between Natural Gas NG and Propane LP To convert from one gas to another consult your Napoleon dealer distributor FIGURE 14 STORM COLL...

Page 13: ...18 WARNING RISK OF ELECTRIC SHOCK Control and valve operate with 110v 1 2 3 4 YELLOW BROWN W H I T E P U R P L E B L A C K IGNITOR WIRE IGNITOR GAS VALVE SWITCH CONTROL MODULE GROUND 110v POWER SUPPL...

Page 14: ...s installed Frame to local building codes To install the fireplace face flush with the finished surface position the framework to accommodate the thickness of the finished surface Use 4 flat head scre...

Page 15: ...from the slots in the door frame to release the top of the door Then pivot forward until the top edge of the door clears the front of the fireplace Next gripping the sides of the door lift the door ou...

Page 16: ...7 Once the frame is perfectly square and the control door will close without rubbing against the sides of the frame tighten all screws 8 Open the control door 9 Insert the door stop chain into the re...

Page 17: ...res into the clips at both sides and the bottom of the frame Use the extra clips provided to retain any loose wires 7 Re attach frame onto unit 8 Remove the control panel by removing the 2 screws secu...

Page 18: ...2 Turn off all electrical power to the fireplace if service is to be preformed 3 Turn manual shut off valve clockwise to off Do not force TO TURN OFF GAS CERTIFIED UNDER CSA 2 22 2007 ANSI 21 50 2007...

Page 19: ...pressure FIGURE 34 FIGURE 33 TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE FIREPLACE CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause imprope...

Page 20: ...LACE 2 INSTALLATION DATE OF FIREPLACE 3 PART NUMBER 4 DESCRIPTION OF PART 5 FINISH FOR WARRANTY REPLACEMENT PARTS A PHOTOCOPY OF THE ORIGINAL INVOICE WILL BE REQUIRED TO HONOUR THE CLAIM IDENTIFIES IT...

Page 21: ...issing and that the seal is tight Check that both 3 and 5 vent liners are free of holes and well sealed at all joints Check that the minimum rise per foot has been adhered to for any horizontal ventin...

Page 22: ...22 W415 0619 B 03 03 08 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...