background image

11

W415-0619 / B / 03.03.08

1.

 Stretch the 3” 

fl

 exible vent pipe to the required length taking into 

account the additional length needed for the 

fi

 nished wall surface. 

Apply a heavy bead of the high temperature sealant W573-0007 
(not supplied).  Slip the 

fl

 exible vent pipe a minimum of 2” over the 

inner sleeve of the air terminal and secure with 3 - #8 screws. 

NOTE:  If using pipe clamps to connect vent components, 3 
screws must also be used to ensure the connection cannot 
slip off.

2.

 Using the 5” 

fl

 exible vent pipe, slide over the outer combustion 

air sleeve of the air terminal and secure with 3 - #8 screws. Seal 
using high temperature sealant W573-0002 (not supplied).

3.

 Insert the 

fl

 exible vent pipe through the 

fi

 restop maintaining the 

required clearance to combustibles.  Secure the terminal to the 
exterior wall (lettering in an upright, readable position) and make 
weather tight by sealing with caulking (not supplied).

4. 

If additional 

fl

 exible vent pipe is required, couple them together 

as illustrated.  The vent system must be supported approximately 
every 3 feet for both vertical and horizontal runs.  Use non-
combustible strapping to maintain the minimum 1” clearance to 
combustibles from the 

fl

 exible vent pipe.

HORIZONTAL AIR TERMINAL INSTALLATION

FIGURE 10

FIGURE 11

USING FLEXIBLE VENT COMPONENTS

USE ONLY WOLF STEEL LTD. 3” / 5” FLEXIBLE VENT COMPONENTS.

Use only approved  

fl

 exible vent pipe kits marked:

“Wolf Steel Approved Venting” as 
identi

fi

 ed by the stamp only on the 

5” 

fl

 exible vent pipe.

For safe and proper operation of the 

fi

 replace, follow the venting 

instructions exactly.
All 3" 

fl

 exible vent pipe and 5" 

fl

 exible vent pipe joints may 

be sealed using high temperature sealant W573-0002 (not 
supplied) or the high temperature sealant W573-0007 Mill 
Pac (not supplied).  However, the high temperature sealant 
W573-0007 Mill Pac (not supplied) must be used on the 
joint connecting the 3" 

fl

 exible vent pipe and the exhaust 

fl

 ue collar. 

FIGURE 9

Four inches (4”) is the minimum bend radius allowed for the  
5” 

fl

 exible vent pipe.

SPACERS

ELBOW

Do not allow the 3" flexible vent pipe to  bunch 
up on horizontal or vertical runs and elbows.  
Keep it pulled tight.  A 1” air gap between the 
3" and 5" flexible vent pipes all around is 
required for safe operation.  A spacer is 
required at the start, middle and end of each 
elbow to ensure this gap is maintained.  
Spacers are attached to the 3" flexible vent 
pipe at predetermined intervals to maintain a 
1” air gap to the 5" flexible vent pipe. These 

spacers must not be removed.

!

WARNING

1

. Fasten the roof support to the roof using the screws 

provided. The roof support is optional. In this case the 
venting is to be adequately supported using either 
an alternate method suitable to the authority having 
jurisdiction or the optional roof support.  Figure 12.

2.

 Stretch the 3" 

fl

 ex vent pipe to the required length. 

Slip the 3" 

fl

 ex vent pipe a minimum of 2” over the inner 

pipe of the air terminal connector and secure with 3 #8 
screws. Seal using a heavy bead of high temperature 
sealant W573-0007 (not supplied).  Figure 13.

NOTE:  If using pipe clamps to connect vent 

components, 3 screws must also be used to ensure the connection cannot slip off.

3. 

 Repeat using the 5" 

fl

 ex vent pipe, using a heavy bead of high temperature sealant 

W573-0002 (not supplied).  Figure 13.

ROOF SUPPORT

FIGURE 12

3” FLEXIBLE

VENT PIPE

5” FLEXIBLE 

VENT PIPE

INNER

PIPE

HIGH

TEMPERATURE

SEALANT

AIR

TERMINAL

CONNECTOR

FIGURE 13

VERTICAL AIR TERMINAL INSTALLATION

Summary of Contents for TORCH GT8P

Page 1: ...y appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot re...

Page 2: ...erials gasoline and other flammable vapours and liquids Under no circumstances should this fireplace be modified This fireplace must not be connected to a chimney flue pipe serving a separate solid fu...

Page 3: ...ents and wearable parts such as blowers gas valves thermal switch switches wiring remote controls ignitor gasketing and pilot assembly are covered and NAPOLEON will provide replacement parts free of c...

Page 4: ...on carpeting vinyl tile or other combustible material other than wood flooring the fireplace shall be installed on a metal or wood panel extending the full width and depth GENERAL INSTRUCTIONS GENERA...

Page 5: ...als on the inner exhaust flue only the outer air intake joints must be sealed using a red high temperature silicone RTV This same sealant may be used on both the inner exhaust and outer intake vent pi...

Page 6: ...ated with the insulation wrapped in a protective sleeve to minimize condensation Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed Use firesto...

Page 7: ...24 2a Horizontal run if vent run includes vertical rise 4 7 FT 2b Vertical run Immediately off the fireplace if 7 FT maximum horizontal run is required 18 7 FT 2b 2c FIGURE 2a 4 MIN 24 MAX 8 18 MAXIMU...

Page 8: ...excluding fireplace and air terminal connections N A 2 Rise per foot recommended 1 4 N A Rise per foot allowable 0 N A Vertical run when not venting horizontally 24 19 1 2 FT 3a 3c Horizontal run 4 5...

Page 9: ...9 W415 0619 B 03 03 08 O O B B G A F C H H L K J M MINIMUM AIR TERNMINAL LOCATION CLEARANCES N D E O FIGURE 4...

Page 10: ...g to cut them Use a plumb bob to line up the center of the openings Do not fill this space with any type of material A vent pipe shield will prevent any materials such as insulation from filling up th...

Page 11: ...e joints may be sealed using high temperature sealant W573 0002 not supplied or the high temperature sealant W573 0007 Mill Pac not supplied However the high temperature sealant W573 0007 Mill Pac not...

Page 12: ...ed Conversion Kits The mobile home appliance is field convertible between Natural Gas NG and Propane LP To convert from one gas to another consult your Napoleon dealer distributor FIGURE 14 STORM COLL...

Page 13: ...18 WARNING RISK OF ELECTRIC SHOCK Control and valve operate with 110v 1 2 3 4 YELLOW BROWN W H I T E P U R P L E B L A C K IGNITOR WIRE IGNITOR GAS VALVE SWITCH CONTROL MODULE GROUND 110v POWER SUPPL...

Page 14: ...s installed Frame to local building codes To install the fireplace face flush with the finished surface position the framework to accommodate the thickness of the finished surface Use 4 flat head scre...

Page 15: ...from the slots in the door frame to release the top of the door Then pivot forward until the top edge of the door clears the front of the fireplace Next gripping the sides of the door lift the door ou...

Page 16: ...7 Once the frame is perfectly square and the control door will close without rubbing against the sides of the frame tighten all screws 8 Open the control door 9 Insert the door stop chain into the re...

Page 17: ...res into the clips at both sides and the bottom of the frame Use the extra clips provided to retain any loose wires 7 Re attach frame onto unit 8 Remove the control panel by removing the 2 screws secu...

Page 18: ...2 Turn off all electrical power to the fireplace if service is to be preformed 3 Turn manual shut off valve clockwise to off Do not force TO TURN OFF GAS CERTIFIED UNDER CSA 2 22 2007 ANSI 21 50 2007...

Page 19: ...pressure FIGURE 34 FIGURE 33 TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE FIREPLACE CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause imprope...

Page 20: ...LACE 2 INSTALLATION DATE OF FIREPLACE 3 PART NUMBER 4 DESCRIPTION OF PART 5 FINISH FOR WARRANTY REPLACEMENT PARTS A PHOTOCOPY OF THE ORIGINAL INVOICE WILL BE REQUIRED TO HONOUR THE CLAIM IDENTIFIES IT...

Page 21: ...issing and that the seal is tight Check that both 3 and 5 vent liners are free of holes and well sealed at all joints Check that the minimum rise per foot has been adhered to for any horizontal ventin...

Page 22: ...22 W415 0619 B 03 03 08 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Reviews: