W415-1472 / 04.21.15
26
EN
!
WARNING
5.1 INSTALLATION INTO A COMBUSTIBLE ENCLOSURE
OUTSIDE AIR IS MANDATORY FOR A COMBUSTIBLE BUILT-IN ENCLOSURE INSTALL.
When installing the insert as a "Built-in" appliance, it is important to maintain the clearances to combustibles,
see "MINIMUM CLEARANCE TO COMBUSTIBLES" section.
A non-combustible hearth must cover the fl ooring underneath, as well as, a minimum of six inches in front and
to both sides of the appliance.
A.
Install
fl oor protection.
B.
Frame structure maintaining minimum clearances. Locate and frame openings for both the exhaust
and outside air. Outside air is mandatory for enclosure installations.
See "OUTSIDE AIR" section.
C.
Refer to vent manufacturer's installation instructions and to "VENTING" section. Connect the vent.
Install fl ashing, see "FLASHING INSTALLATION" section.
D.
Consideration must be taken during installation that removal of the insert is necessary for inspection
and annual maintenance. Install the vent cap.
33”
40”
MINIMUM
ENCLOSURE
HEIGHT
17”
27”
3 1/2” MAX
3 1/2”
MAX
Non
combustible
floor protection.
This protection must
offer an R value of 0.4 (two
layers of 1/2” thick cement board, total 1” with each layer rated with an
R value of 0.2).
For temperature requirements, the enclosure space around and
above the heater must be left unobstructed.
Centerline of
heater opening
2”
4 7/8”
1 7/8”
7 1/8”
Summary of Contents for NPI45
Page 48: ...W415 1472 04 21 15 48 EN 67 20 29 58 41 38 43 44 63 57 60 6 11 3 NPI45 REPLACEMENT PARTS...
Page 54: ...W415 1472 04 21 15 54 EN 14 0 SERVICE HISTORY 43 1...
Page 55: ...W415 1472 04 21 15 55 EN 15 0 NOTES 44 1...
Page 106: ...106 W415 1472 04 22 15 FR 67 20 29 58 41 38 43 44 63 57 60 6 11 3 PI CES DE RECHANGE DU NPI45...
Page 114: ...114 W415 1472 04 22 15 FR 15 0 NOTES 44 1...
Page 115: ...115 W415 1472 04 22 15 FR 44 1...