4.5.1 HORIZONTAL EXHAUST THROUGH WALL INSTALLATION
4.5.2 THROUGH THE WALL WITH VERTICAL RISE / HORIZONTAL TERMINATION
Floor
Protection
12” Minimum
Outside Air
(Recommended)
6”
Minimum
3” Minimum
Wall
Thimble
11 5/8”
5’ Maximum
17”
Wall Thimble
Outside Air
(Recommended)
3”
2”
Floor
Protection
6”
Minimum
11 5/8”
17”