background image

32

W415-0341 / F / 11.21.05

P

I

A

B

PILOT

N

O

L

O

T

H I

L O

FF

O

Main burner goes
out; pilot goes out.

Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"

Vent is blocked
Vent is re-circulating

-  check for vent blockage.
-  check joint seals and installation.

4" flexible vent has be-
come disconnected from
fireplace.
Excessive air flow around
the pilot burner.

-  re-attach to fireplace.

Flames are con-
sistently too large
or too small.
Carboning oc-
curs.

-  check pressure readings:
Inlet pressure can be checked by turning screw (A) counter-clock-
wise 2 or 3 turns and then placing pressure gauge tubing over the
test point. Gauge should read 7" (minimum 4.5") water column for
natural gas or 13" (11" minimum) water column for propane. Check
that main burner is operating on "HI".
Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5" water column for natural gas or 10" water
column for propane. Check that main burner is operating on "HI".
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN
SCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOT
OVERTORQUE.
Leak test with a soap and water solution.

Unit is over-fired or under-
fired.

Carbon is being
deposited on
glass, logs or
c o m b u s t i o n
chamber sur-
faces.

Flame is impinging on the
logs or combustion cham-
ber.

-  check that the logs are correctly positioned.
-  open air shutter to increase the primary air.
-  check the input rate: check the manifold pressure and orifice size
as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that the
seal is tight.
- check that both 4" and 7" vent liners are free of holes and well
sealed at all joints.
- check that minimum rise per foor has been adhered to for any
horizontal venting.

Air shutter has become
blocked

-  ensure air shutter opening is free of lint or other obstructions.

White / grey film
forms.

Sulphur from fuel is being
deposited on glass, logs
or combustion chamber
surfaces.

-  clean the glass with a gas fireplace glass cleaner. DO NOT CLEAN
GLASS WHEN HOT.
If deposits are not cleaned off regularly, the glass may become per-
manently marked.

Exhaust fumes
smelled in room,
headaches.

Fireplace is spilling.

- check door seal and relief flap seal.
- check for chimney blockage
- check that chimney is installed to building code.
- room is in negative pressure; increase fresh air supply.

Main burner
flame is a blue,
lazy, transparent
flame.

Blockage in vent.

-  remove blockage. In really cold conditions, ice buildup may occur
on the terminal and should be removed as required.

-  refer to Figure 15 to ensure correct location of storm collars.

Incorrect installation.

Remote wall
switch is in "OFF"
position; main
burner comes on
when gas knob is
turned to "ON" po-
sition.

Wall switch is mounted up-
side down

- reverse.

Faulty valve.

- replace.

- replace.

Remote wall switch is
grounding.

- check for ground (short); repair ground or replace wire.

Remote wall switch wire is
grounding.

SYMPTOM

PROBLEM

TEST SOLUTION

- Restrict vent exit. See "

RESTICTING VERTICAL VENTS

".

- VENT HEIGHT MORE THAN 15 FEET: restrict vent exit using
restrictor plate kit RP34-KT

MODEL GD33 ONLY:
BGD34 & GD34:

 

Aggressive

venting action due to vent height.

Flames are very
aggressive.

- tighten screws holding door in place

Door is ajar

-  rotate the restrictor plate into position 

(34s only p.18)

.

-  install the restrictor plate supplied with the unit 

(BGD33 only p.19)

.

Summary of Contents for BGD33NR

Page 1: ...try to light any appliance Do not touch any electrical switch Do not use any phone in your build ing Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions...

Page 2: ...hing or other flammable material should not be placed on or near the fireplace Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace It is imperative that...

Page 3: ...the prior approval of an authorized company official Labour costs to the account of the prior approval of an authorized company official Labour costs to the account of NAPOLEON NAPOLEON NAPOLEON NAPO...

Page 4: ...on and it is important to know the specifics that apply to your area for example in Massachusetts State The fireplace damper must be removed or welded in the open position prior to installation of a f...

Page 5: ...TERMINAL KIT GD222 VENTING LENGTHS AND AIR TERMINAL LOCATIONS VENTING The maximum allowable vertical vent length is 40 feet For optimum flame appearance and fireplace performance keep the vent length...

Page 6: ...r ignition Six 6 inches is the minimum bend radius allowed for the 7 diameter flexible liner For optimum performance it is recommended that horizontal runs have a minimum inch rise per foot when using...

Page 7: ...at open Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance...

Page 8: ...i cal rise to m a x i m u m of 40 feet vertical rise is equal to or greater than the horizontal run horizontal run verti cal rise to m a x i m u m of 40 feet vertical rise is equal to or greater than...

Page 9: ...ONS ELBOW VENT LENGTH VALUES Example 1 See graph to determine the required vertical rise VT for the required horizontal run HT For vent configurations requiring more than two 90 el bows the following...

Page 10: ...Formula 2 HT VT 24 75 feet 20 45 24 75 Since both formulas are met this vent configuration is ac ceptable FIGURE9 For vent configurations requiring more than two 90 elbows the following formulas appl...

Page 11: ...T VT Formula 2 HT VT 40 feet 90 90 Example 3 V1 3ft V2 8ft VT V1 V2 3 8 11 ft H1 2 5ft H2 2ft HR H1 H2 2 5 2 4 5 ft HO 03 three 90 elbows 90 03 270 90 5 4 ft HT HR HO 4 5 5 4 9 9 ft HT VT 9 9 11 20 9...

Page 12: ...raph to determine the required ver tical rise VT for the required horizontal run HT ceptable Example 5 V1 4ft V2 1 5ft VT V1 V2 4 1 5 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5...

Page 13: ...03 90 90 90 90 5 4 ft HT HR HO 5 5 5 4 10 9 ft HT VT 10 9 15 25 9 ft Formula 1 HT VT 10 9 15 Formula 2 HT VT 40 feet 25 9 40 Since both formulas are met this vent configuration is ac ceptable FIGURE1...

Page 14: ...VT 3 x 4 5 13 5 ft 16 1 13 5 Since this formula is not met this vent configuration is unac ceptable Formula 2 HT VT 40 feet 20 6 40 Since only formula 2 is met this vent configuration is unac ceptable...

Page 15: ...e vent pipe collar down to cover up the open end of the shield and tighten This will prevent any materials such as insulation from filling up the 1 air space around the pipe For optimum performance it...

Page 16: ...ed length taking into account the additional length needed for the finished wall surface Slip the liner a mini mum of 2 over the inner sleeve of the air terminal and secure with 3 8 screws Apply a hea...

Page 17: ...Napoleon support ring assembly W010 0370 or equivalent noncombustible strap ping to maintain the minimum clearance to combustibles for both vertical and horizontal runs FIGURE31 5 Remove nails from th...

Page 18: ...eather tight by sealing with caulking Where possi ble cover the sides and top edges of the flashing with roof ing material 8 Apply a heavy bead of waterproof caulking 2 inches above the flashing Slide...

Page 19: ...IGURE37 GAS INSTALLATION MOBILE HOME INSTALLATION WIRE SIZE MAX LENGTH 14 gauge 100 feet 16 gauge 60 feet 18 gauge 40 feet FRAMING In Canada manufactured mobile home installation may be vented horizon...

Page 20: ...D33 GD34 BGD34 FIGURE39a d FIGURE40a d GD34 Finishing must be done using a non combustible material placed flush with the front face of the unit and extending from the top of the unit Example cement b...

Page 21: ...43 c Additional set screws may be installed TOP SLOT FINISHING MATERIAL CORNER POST NAILING TAB A B C CENTRE HOLE BGD33 NAILING TAB INSTALLATION It is best to frame your fireplace after it is position...

Page 22: ...ombustible materials must be installed flush with the front of the fireplace but must not cover any of the black face area of the fireplace Non combustible material brick stone or ceramic tile may pro...

Page 23: ...upport Position the top of the log into the pocket provided on the top of the rear log 1 Position the notch located in the bottom end of log 3 against the centre grate post Rest the top of log 3 into...

Page 24: ...entre grate post Rest the top of log 3 into the pocket at the top end of log 2 Place the bottom of log 4 onto the locating pin on the right side of the log support Rest the top into the pocket pro vid...

Page 25: ...he clips along the top of the louvre opening Secure using a screw through the centre slot NOTE Hood W335 0028 is re quired on B GD34 models Hood W335 0028 is recommended but not required on B GD33 mod...

Page 26: ...the fireplace base or the firebox Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the se curing stud at the bottom left of the unit using a...

Page 27: ...sult in a fire or explosion D Do not use this fireplace if any part has been under water Immediately call a qualified service technician to inspect the fireplace and replace any part of the control sy...

Page 28: ...mmable vapours and liquids The flow of combustion and ventilation air must not be obstructed 1 In order to properly clean the burner and pilot assembly remove the logs to expose both assemblies 2 Keep...

Page 29: ...PROPANE GAS VALVE 25 W010 0595 BURNER 29 W135 0082 LOG 5 CHARCOAL PIECE 30 W135 0182 LOG 6 23 W500 0096 FIRESTOP SPACER 32 W500 0208 RESTRICTOR PLATE ACCESSORIES FLEXIBLE VENT KITS TERMINAL KITS ROOF...

Page 30: ...30 W415 0341 F 11 21 05 NOTE SOME PARTS NOT EXACTLY AS SHOWN...

Page 31: ...ve replace Wall switch wiring is de fective disconnect switch wires from valve connect a jumper wire across terminals 1 3 if the main burner lights check the wires for de fects and or replace wires Pi...

Page 32: ...and 7 vent liners are free of holes and well sealed at all joints check that minimum rise per foor has been adhered to for any horizontal venting Air shutter has become blocked ensure air shutter open...

Reviews: