![Nanometrics RM-4 User Manual Download Page 51](http://html.mh-extra.com/html/nanometrics/rm-4/rm-4_user-manual_705058051.webp)
Filling up the log ringbuffer.
On its startup the RM-4 pre-allocates some of its internal memory to be used
as a memory ringbuffer. This is done during the factory test.
Software reboot.
The RM-4 is performing a software reboot. At each software reboot the
internal log and SOH ringbuffer is reinitialized.
Waiting for reboot.
The RM-4 shut down all its processes and will shortly reboot.
Have consolidated all update exceptions.
The RM-4 has found that all parameters in the configuration sent by the
RM-4 user interface are within the allowable limits. The message is generated
after all values are checked.
Warning
PacketSender
Error sending to
[IP address].
The RM-4 cannot send packets to the host at the IP address specified in the
message. Check if the host is up and running, if the host is connected to the
network and if route between the RM-4 and the host exists.
RM4
Failed to load saved config.
The RM-4 was unable to load the configuration saved in the flash memory
and is using the default configuration in its code. Reconfigure the RM-4
using the RM-4 user interface since the default configuration does not
contain any information specific to the existing network. Set the RM-4 to its
correct IP address first, and then configure the other components in its
configuration. Once tested, the new configuration should be stored
permanently with a “Commit Config” action.
Failed to overwrite config.
After receiving a Commit command from the RM-4 user interface, the RM-4
was unable to overwrite the configuration saved in the flash memory with
the currently operating configuration. Send Commit command from the RM-4
user interface again.
TelemetryPacketReader
Serial port
[port number]
driver write error.
There was a write error on the serial port. The message from NAQS was not
sent to the HRD connected to the port specified in the message. If it is a
retransmit request, NAQS will reissue the retransmission request when the
time-out configured in the NAQS station file expires. If the message is a
mass centering or calibration command, reissue the command.
RM-4 Manual 45
Appendix D - Instrument Log Messages
Summary of Contents for RM-4