![NAiS FP2 Technical Manual Download Page 99](http://html2.mh-extra.com/html/nais/fp2/fp2_technical-manual_3062214099.webp)
7-5
7.2 Setting the Opera tion Mode and Baud Rate
7.2.1
Setting using Mode Speed Setting Switch
The operation mode is set using the mode speed setting switch.
Setting general-purpose serial communicaiton mode
When COM. 1 and COM. 2 are both set to the general-purpose serial communicaiton mode:
COM. 1
COM. 2
1
2
5
6
ON
ON
ON
ON
•
The computer link mode can be changed to the general-purpose serial communication mode using the
F159 (MTRN) instruciton.
Reference:
<8.2 Setting Communicaiton Conditions and Monitoring>
Setting baud rate
Baud rates for COM. 1 and COM. 2 ports are specified using the mode speed setting switch. The
allowable baud rates specified with the switch are 9600 bps, 19200 bps and 115200 bps.
The settings for each baud rate are as below.
COM. 1
COM. 2
Baud rate
3
4
7
8
115200 bps
OFF
OFF
OFF
OFF
19200 bps
ON
OFF
ON
OFF
9600 bps
OFF
ON
OFF
ON
Memory switch
ON
ON
ON
ON
Note) The values specified with this switch will be effective when the power turns on.
Setting communication format
The other formats are as below. (Default settings)
Setting
Setting value
Unit No.
1
Baud rate
9600 bps
Character bit
8 bits
Parity
Odd
Stop bit
1 bit
RS/CS (Only when using RS232C)
Invalid
Send waiting time
0.00 ms
Header
STX not exist
Terminator
CR
Initialize modem
No
Note) The above setting values can be changed using the memory switch.
Note:
The mode speed setting switch is at the back of Multi Communication Unit.
Summary of Contents for FP2
Page 2: ......
Page 8: ......
Page 9: ...Chapter 1 Functions and Restrictions of the Unit...
Page 14: ...1 6...
Page 15: ...Chapter 2 Specifications and Functions...
Page 29: ...Chapter 3 Installation and Wiring of Communication Blocks...
Page 35: ...Chapter 4 Communication Function...
Page 36: ...4 2...
Page 44: ...4 10 4 4 4 Flow Chart...
Page 46: ...4 12...
Page 47: ...Chapter 5 Communication Function PC PLC Link...
Page 65: ...Chapter 6 Communication Function General purpose Serial communication...
Page 94: ...6 30...
Page 95: ...Chapter 7 Communication Function Computer link...
Page 108: ...7 14...
Page 109: ...Chapter 8 Applications...
Page 118: ...8 10...
Page 119: ...Chapter 9 Specifications...
Page 139: ...Chapter 10 Dimensions and Sample Programs...
Page 141: ...10 3 10 1 2 Communication Blocks FP2 CB232 AFP2803 FP2 CB422 AFP2804 FP2 CB485 AFP2805...
Page 142: ...10 4...