![NAiS FP2 Technical Manual Download Page 87](http://html2.mh-extra.com/html/nais/fp2/fp2_technical-manual_3062214087.webp)
6-23
6.7.2 Connection Example with External Device <1:1 Communication with FP
Series PLC >
Overview
Connect the FP2/FP2SH and another FP series PLC using the RS232C interface and the MEWTOCOL-
COM communication protocol.
•
When the data area read comm and “%01#RDD00000 00001**
C
R
” is sent from the FP
Σ
side, the
values of the data register of the PLC connected to the system are sent as a response. For example, if
the value K100 is stored in DT0 and the value K200 is stored in DT1 of the PLC,
“%01$RD6400C8006F
C
R
” is sent as a response to the command. If there is an error, “%01!
○○
**
C
R
” is
returned (
○○
is the error code).
•
In addition to data area read an d write commands, MEWTOCOL-COM also provides contact area read
and write as well as many other commands.
System register settings of FP series PLCs (FP1, FP1 side)
In the default settings, the COM port is set not to be used. For 1:1 general-purpose serial communication,
the system registers should be set as shown below.
Communication format settings for FP series PLC (FP0, FP1)
No.
Name
Set Value
No. 412
COM port 1 selection of communication mode
Computer link
No. 413 *
Communication format for COM port
Character bit: ……
Parity check: …..
Stop bit: …………
Terminator: ……..
Header: …………
8 bits
Odd
1 bit
CR
STX not exist
No. 414 *
Baud rate for COM port
19200 bps
* These settings should be the same as the settings of the connected MCU.
Connection to FP series PLCs (FP0, FP1)
<Using AFP2803> RS232C
•
- Connection with FP0 COM po rt
Summary of Contents for FP2
Page 2: ......
Page 8: ......
Page 9: ...Chapter 1 Functions and Restrictions of the Unit...
Page 14: ...1 6...
Page 15: ...Chapter 2 Specifications and Functions...
Page 29: ...Chapter 3 Installation and Wiring of Communication Blocks...
Page 35: ...Chapter 4 Communication Function...
Page 36: ...4 2...
Page 44: ...4 10 4 4 4 Flow Chart...
Page 46: ...4 12...
Page 47: ...Chapter 5 Communication Function PC PLC Link...
Page 65: ...Chapter 6 Communication Function General purpose Serial communication...
Page 94: ...6 30...
Page 95: ...Chapter 7 Communication Function Computer link...
Page 108: ...7 14...
Page 109: ...Chapter 8 Applications...
Page 118: ...8 10...
Page 119: ...Chapter 9 Specifications...
Page 139: ...Chapter 10 Dimensions and Sample Programs...
Page 141: ...10 3 10 1 2 Communication Blocks FP2 CB232 AFP2803 FP2 CB422 AFP2804 FP2 CB485 AFP2805...
Page 142: ...10 4...