![NAiS FP2 Technical Manual Download Page 18](http://html2.mh-extra.com/html/nais/fp2/fp2_technical-manual_3062214018.webp)
2-4
2.2 FP2 Communicati on Blocks
2.2.1
Types of Communication Blocks
There are three types of communication cassettes, each having a particular field of application.
FP2 communication block (RS232C) FP2-CB232 (AFP2803)
This communication block is a 1-channel unit with a five-wire RS232C port. It supports 1:1 computer
links, general-purpose serial communication and PC(PLC) link between two units. RS/CS control is
possible in general-purpose serial communication mode.
Pin No.
Name
Abbr.
Signal direction
1
(Not connected)
(NC)
2
Send Data
SD
Unit to external devices
3
Receive Data
RD
External devices to Unit
4
Request to Send
RS
Unit to external devices
5
Clear to Send
CS
External devices to Unit
6
(Connection
unavailable)
-
7
Signal Ground
SG
8
(Connection
unavailable)
-
9
Data terminal ready
ER
Unit to external devices
Note1) RS (Request to Send) is controlled at Y contact.
Note2) When setting the RS/CS control to “Able”, data cannot be sent without the pin CS (Clear to Send).
When using with a three-wire port, short-circuit the pin RS and CS, or disable them.
Note3) The ER signal is shorted in the RS signal and the communication block.
Note4) Do not connect to the pin “connection unavailable”.
Note5) The shell part and the mounting screw part of the connector is connected to the ground terminals
of the power supply unit.
FP2 communication block (RS422) FP2-CB422 (AFP2804)
This communication block is a 1-channel unit with a four-wire RS422 port. It supports 1:1 computer link,
general-purpose communication and PC(PLC) link (MEWNET-W0) between two units.
Pin No.
Name
Abbr.
Signal direction
1
(Not connected)
(NC)
2
Send Data
SD+
Unit to external devices
3
Receive Data
RD+
External devices to Unit
4
Send Data
SD-
Unit to external devices
5
Receive Data
RD-
External devices to Unit
6
(Connection
unavailable)
-
7
(Connection
unavailable)
-
8
(Connection
unavailable)
-
9
(Connection
unavailable)
-
Unit to external devices
Note) The shell part and the mounting screw part of the connector is connected to the ground terminals
of the power supply unit.
Summary of Contents for FP2
Page 2: ......
Page 8: ......
Page 9: ...Chapter 1 Functions and Restrictions of the Unit...
Page 14: ...1 6...
Page 15: ...Chapter 2 Specifications and Functions...
Page 29: ...Chapter 3 Installation and Wiring of Communication Blocks...
Page 35: ...Chapter 4 Communication Function...
Page 36: ...4 2...
Page 44: ...4 10 4 4 4 Flow Chart...
Page 46: ...4 12...
Page 47: ...Chapter 5 Communication Function PC PLC Link...
Page 65: ...Chapter 6 Communication Function General purpose Serial communication...
Page 94: ...6 30...
Page 95: ...Chapter 7 Communication Function Computer link...
Page 108: ...7 14...
Page 109: ...Chapter 8 Applications...
Page 118: ...8 10...
Page 119: ...Chapter 9 Specifications...
Page 139: ...Chapter 10 Dimensions and Sample Programs...
Page 141: ...10 3 10 1 2 Communication Blocks FP2 CB232 AFP2803 FP2 CB422 AFP2804 FP2 CB485 AFP2805...
Page 142: ...10 4...