![NAiS FP2 Technical Manual Download Page 93](http://html2.mh-extra.com/html/nais/fp2/fp2_technical-manual_3062214093.webp)
6-29
6.9 Troubleshooting ( General-purpose Serial
Communication)
Status indicator LEDs
Indication
Function
Light (on): when reception error occurs
ERR
Red
Communication error
Off: when received data was retrieved
Light (on): when setting error occurs
S. ERR
Red
Setting error
Off: Normal
Note) The details can be checked by monitoring the MCU status using F161 (MRCV) instruction.
Troubleshooting
Trouble
Contents to check
How to confirm
Is a communciation block installed?
Check if the communication
block is installed firmly.
Is the wiring correct?
Check the wiring again.
Communication is not
possible.
(ERR LED lights)
Isn’t there any problem in
environments such as noise?
Check the shielding.
S. ERR lights
- Is the operation mode setting
correct?
- Isn’t it used excessively ignoring the
usage restrictions?
Read out and check the status
using F161 (MRCV) instruction.
Isn’t the request to send given
redundantly during transmission?
In case of RS232C communication
block, isn’t transmission forbidden by
CTS signal?
Isn’t operation error occurring when
executing MTRN instruction?
Review the program.
Is the setting for the communication
conditions the same as the one for the
device communicated?
Transmission is not
possible.
Is the setting of the method for
detecting “reception done” the same
as the one for the device
communicated?
Check the setting reading the
status using F161 (MRCV)
instruction.
Isn’t reception error occurring?
Isn’t the reception buffer FULL error
occurring?
If the error occurs, the operation
cannot be restarted without performing
CH reset.
Is the operation mode general-
purpose communication?
(Has the operation mode been
changed using MTRN instruction?)
Check the setting reading the
status using F161 (MRCV)
instruction.
Reception is not possible.
When data is not received properly:
(Isn’t it multiplex reception? Isn’t there
garbage in the buffer cuased by noise
or something?)
Review the program.
Check the setting reading the
status using F161 (MRCV)
instruction.
ALARM lights
Hardware error
Please contact your dealer.
Summary of Contents for FP2
Page 2: ......
Page 8: ......
Page 9: ...Chapter 1 Functions and Restrictions of the Unit...
Page 14: ...1 6...
Page 15: ...Chapter 2 Specifications and Functions...
Page 29: ...Chapter 3 Installation and Wiring of Communication Blocks...
Page 35: ...Chapter 4 Communication Function...
Page 36: ...4 2...
Page 44: ...4 10 4 4 4 Flow Chart...
Page 46: ...4 12...
Page 47: ...Chapter 5 Communication Function PC PLC Link...
Page 65: ...Chapter 6 Communication Function General purpose Serial communication...
Page 94: ...6 30...
Page 95: ...Chapter 7 Communication Function Computer link...
Page 108: ...7 14...
Page 109: ...Chapter 8 Applications...
Page 118: ...8 10...
Page 119: ...Chapter 9 Specifications...
Page 139: ...Chapter 10 Dimensions and Sample Programs...
Page 141: ...10 3 10 1 2 Communication Blocks FP2 CB232 AFP2803 FP2 CB422 AFP2804 FP2 CB485 AFP2805...
Page 142: ...10 4...