Opus Control Wiring and Programming Installation Manual 

www.NabcoEntrances.com

P/N C-00139 

Rev 10-20-17

Programming Issues

Problem

Possible Solution

Double Egress pairs are not 

Synchronizing

X

Software Revision (up to, and including 20)

• Remove CANbus cable. Set both Controls as single doors. The activation signal should 

be paralleled between both Controls. Safety signals should only be attached to their 

corresponding door’s Control.

X

Software version is 21

• Be sure both controls are set to “Double Egress”. Safety signals should only be attached to 

their corresponding door’s control.

• See also “Sim Pair behaves oddly” located at top of this Table.

Error Messages

Error Msg

Description

Resolution

Recycle Warning

Recycle was detected more than (5) times while 

opening or closing cycle continuously.

X

Check Door resistance and Door Path for 

resistance to movement.

• It may be necessary to adjust the Recycle 

Sensitivity.

MPU

Microprocessor detects errors within the Internal or 

External Circuits.

X

This could be a random error.

• If the Error occurs repeatedly, please replace 

the Opus Control.

Drive Circuit

If the Drive Circuit detects an unusual state, the 

Opus will stop door movement. Possible causes are:

X

Abnormal voltage at Motor Circuit

X

Abnormal current draw from motor.

X

Check all connections between the Control 

 

and Motor. 

X

Check Motor Fuse

X

Check motor for open circuit, short circut, or 

short to ground.

X

It is possible electrical noise may cause a false 

error. If the error does not occur repeatedly 

then it’s most likely not an issue.

Communication

X

CAN-bus Communication Error

X

Can happen in Simultaneous Pair applications.

Check the CAN-bus Cable between the two Opus 

Controls.

61 Sensor

X

Incorrect sensor wiring related to that input.

Incorrect settings on sensor and/or control 

related to sensor monitoring.

X

Sensor has failed.

Check sensor wiring.

Check settings on sensor and/or control 

related to sensor monitoring.

Try a new sensor.

62 Sensor
6B Sensor
SWL Sensor

Notice: If after troubleshooting a problem, and a satisfactory solution cannot be achieved, please call 

Nabco Entrances at 1-877-622-2694 between 8 am – 4:30pm Central time for additional assistance. 

 

DO NOT leave any problem unresolved. If the door cannot be repaired immediately, turn off the 

door and leave it inoperable until repairs can be made. Advise the owner NOT to operate the door 

in the automatic mode until repairs are effected. NEVER leave a door operating without all safety 

detection systems operational.

Summary of Contents for Opus Control

Page 1: ...HAPTER 1 SAFETY 2 CHAPTER 2 SCOPE 3 SECTION 2 1 To the Installer 3 SECTION 2 2 Objective 3 CHAPTER 3 FEATURES 3 CHAPTER 4 SPECIFICATIONS 3 SECTION 4 1 General Specifications 3 SECTION 4 2 Electrical S...

Page 2: ...esult in seriouc personal or fatal injury When uncertain whether power supply is disconnected always verify using a voltmeter Do not place finger or uninsulated tools inside the electrical controller...

Page 3: ...nd Folding Doors X X Existing swing and folding doors using Analog Magnum or U01 U19 controls works with encoders or microswitches X X Existing sliding doors using U01 U19 controls Retrofit kits can b...

Page 4: ...er 24 VAC P N A 01185 The Opus Control must Not be used to output power to X X Magnetic Locks X X Electric Strikes To determine if an auxiliary power supply must be used add the total current draw of...

Page 5: ...of Header End Cap Attention Electrical circuit to Nabco operator must not be not shared with other equipment such as lighting cash registers or any device that might cause electrical interference on t...

Page 6: ...Communication 7 CN1 Power Connector 4 Rotary Dial 8 Fuse CHAPTER 7 THE ROTARY DIAL X X Push down on the Rotary Dial Long push 2 seconds to gain access to LCD Catagory Screens Short push under 2 second...

Page 7: ...lose Recycle Cnt Latest Recycle Posi on DN 1334 LEVEL 4 Push and Hold Rotary Dial 2 Sec Rotate Dial Rotate Dial Rotate Dial Short Push Figure 3 LCD Screen Transition SECTION 8 1 Level One Specificatio...

Page 8: ...oke Learning Go to Se ng menu Reset to Default Set Yes No Passcode Stroke Learning Yes No Ac vate Passcode Rotate Dial Rotate Dial Rotate Dial Figure 6 Level Two Screen Attention To prevent tampering...

Page 9: ...oints should happen Stroke Learning is also used to determine if an existing Operator Type is correct and or to determine if Handing is correct 1 Briefly press down on the Rotary Dial to select X X Ye...

Page 10: ...ly Open X X Slide Door 1 to 13 3 4 of Fully Open Close Speed 0 7 3 The higher the number the faster the Door closes Latch Check Speed 0 7 3 Sets door speed during latch check Latch Check Range 0 7 3 X...

Page 11: ...essure Manual Open Function No Action No Action Does nothing Push and Go P G Enables push and go Stop and Close S C Door pauses at open angle then closes Open Assist X X Assisted Power from motor when...

Page 12: ...X X Sensor Monitoring N C X X BEA Bodyguard Output Full Open X X Output doesn t change state X X Output changes when fully closed X X Output changes when door is closing X X Output changes when door...

Page 13: ...e to reduced open Emergency Close Forces the door to slowly close and lock if equipped Hold Open Mode Causes the door to hold open forever Input H Open Timer N A Same as Open Timer 0 thru 10 12 15 20...

Page 14: ...or slide doors it displays the position in inches from closed Test Open Tests Open Close door cycle while ignoring Safety Signals CHAPTER 9 COMMON PROGRAM ADJUSTMENTS SECTION 9 1 Stroke Learning UNIT...

Page 15: ...PECS Passcode Go to Se ng menu Stroke Learning Yes No Push and Hold Rotary Dial 2 Sec LEVEL 1 LEVEL 2 1 Rotate Dial to select Go to Se ng menu 2 Push Rotary Dial Se ng Category LEVEL 3 History Se ng P...

Page 16: ...Sequential activation Signal to open Signal to close 10 H Programmable input 11 M0 Mode 0 When grounded puts door into One Way Mode Hold Open when grounded with M1 12 M1 Mode 1 When grounded puts door...

Page 17: ...17 of 32 www NabcoEntrances com Opus Control Wiring and Programming Installation Manual Rev 10 20 17 P N C 00139 SECTION 10 2 Switches and Sensors with Monitoring DN 1895...

Page 18: ...ces Non Powered Activation Devices WARNING Total Power Consumption Of All Sensors And Powered Activation Devices Must Not Exceed 750 mA 7 6 5 4 3 2 1 3 2 4 All Device Outputs Must Be N O Dry Contact 7...

Page 19: ...3 2 1 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Exterior Push Plate Interior Push Plate COM N O COM N O All Devices Must Be N O Dry Contact Powered Activation Devices sensor card reader radio receiver etc Powe...

Page 20: ...or Slide Door Sidelite Sensor 7 Out1 Programmable Output 14 13 12 11 10 9 8 7 6 5 4 3 2 1 7 6 5 4 3 2 1 2 4 COM N O PWR PWR 1 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor CO O PWR...

Page 21: ...com Opus Control Wiring and Programming Installation Manual Rev 10 20 17 P N C 00139 SECTION 11 4 Safety with Monitoring Door Mounted Swing Side Sensor Door Mounted Approach Side Sensor Overhead Swing...

Page 22: ...4 13 12 11 10 9 8 7 6 5 4 3 2 1 Fail Secure Electric Strike Fail Secure Lock Shown Fail Safe and Mag Locks will use N C instead of N O Power Supply For Electric Strike N O COM N C Varistor MOV TVS DO...

Page 23: ...G TOTAL POWER CONSUMPTI ON OR ALL SENSORS MUST NOT EXCEED 750 mA ON OFF Hold Open Switch P N A 00805 COM N O PWR PWR COM N O PWR PWR COM N O PWR PWR COM N O PWR PWR va on Sensor Overhead Swing Side Se...

Page 24: ...24 of 32 Opus Control Wiring and Programming Installation Manual www NabcoEntrances com P N C 00139 Rev 10 20 17 SECTION 11 7 Single Full Automatic with Monitoring DN 1658...

Page 25: ...N O PWR PWR 1 RED BLUE BLACK 14 13 12 11 10 9 8 8 WHITE 14 13 12 11 10 9 8 7 6 5 4 3 2 1 6 4 5 COM N O PWR PWR Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor COM N O PWR PWR COM N O...

Page 26: ...26 of 32 Opus Control Wiring and Programming Installation Manual www NabcoEntrances com P N C 00139 Rev 10 20 17 SECTION 11 9 Simultaneous Pair Full Automatic with Monitoring DN 1660...

Page 27: ...430 Clear A 70430 Dark Bronze RED BLACK 14 13 12 11 10 9 8 8 WHITE Off Hold Open On Off 14 13 12 11 10 9 8 8 14 BA break out input must be set to N C on the Opus Control is by default Panic Latch must...

Page 28: ...r connecting to a second Opus for Sim Pair Astragal Sequencing 14 13 12 11 10 9 8 10 14 Example of a switch being used to turn on off Power Close and Hold Closed Programmable input H terminal 10 would...

Page 29: ...irm that IN or EXT highlights when an activation signal isapplied If not check the wiring or the activation device X X At the main screen determine if BA is highlighted If a 4 wire on off hold openswi...

Page 30: ...he Opus will stop door movement Possible causes are X X Abnormal voltage at Motor Circuit X X Abnormal current draw from motor X X Check all connections between the Control and Motor X X Check Motor F...

Page 31: ...00888 CONTROLLER OPUS W CHASSIS BRAKE 9 M 01072 HARNESS POWER MAGNUM BOARD 10 V 00713 Used on A 01249 FUSE 2 AMP 5X20MM 250V FAST ACTING 11 A 01249 Used on GT710 8710 only HARNESS MOTOR OPUS 710 12 A...

Page 32: ...T 10 7 M 01680 HARNESS OPUS CONTROL SIM PAIR 8 A 01098 CONTROLLER W BRAKE BOTTOM LOAD OPUS 9 M 01735 PLATE BOTTOM LOAD OPUS 10 A 01143 CONTROLLER W O BRAKE BOTTOM LOAD OPUS 11 A 01003 Not used on GT71...

Reviews: