background image

  

13 of 32

www.NabcoEntrances.com

OpusControlWiringandProgrammingInstallationManual

Rev. 10-20-17 

P/N C-00139

Input Settings

Parameter

Terminal

Range

Default

Sequential Input

Takes on activation to open then another to close door

Input 62

Terminal 4 Open Slow

Exterior 

Activation

Causes slow opening of the door

Safety with Lockout

Swing side header mounted sensor input

Continuous Safety

Swing side door mounted sensor input

Reduced Opening

Causes unit to change to reduced open

Emergency Close

Forces the door to slowly close and lock (if equipped)

Hold Open Mode

Causes the door to hold open forever

Input 62

Open Timer

N/A

Same as Open Timer,

 

0 thru 10, 12,15, 20,25 sec

Same as 

Open timer

Hold open time for Input 62

Input H Setting

Terminal 

10

— — 

— — 

No input

All Activation Mode

Activates in all modes but OFF

Interior Activation

Activation on interior for One Way mode

Exterior Activation

Activation on exterior

Beam Sensor

Beam input

LE Approach Sensor

LE door mounted sensor

Unlock Input

Receives unlocked signal from elec Lock

Spring Close Only

Turns off power close and hold close

Sequential Input

Takes on activation to open then another to close door

Open Slow

Causes slow opening of the door

Safety with Lockout

Swing side header mounted sensor input

Continuous Safety

Swing side door mounted sensor input

Reduced Opening

Causes unit to change to reduced open

Emergency Close

Forces the door to slowly close and lock (if equipped)

Hold Open Mode

Causes the door to hold open forever

Input H

Open Timer

N/A

Same as Open Timer,

 

0 thru 10, 12,15, 20,25 sec

Same as 

Open timer

Open Timer Setting for this Terminal only

Input 61 Circuit

N/A

X

Normally Open

X

Normally Close

Normally

Open

Circuit logic for Input 61

Input 62 Circuit

N/A

X

Normally Open

X

Normally Close

Normally

Open

Circuit logic for Input 62

Input 6B Circuit

N/A

X

Normally Open

X

Normally Close

Normally

Open

Circuit logic for Input 6B

Input 

 

SWL Circuit

N/A

X

Normally Open

X

Normally Close

Normally

Open

Circuit logic for Input SWL

Insert BA Circuit

N/A

X

Normally Open

X

Normally Close

Normally

Closed

Circuit logic for Input SWL

6B Stop Closing

N/A

X

Yes

No

Determines door movement stop or close, when 6B is 

ON at latch check while closing cycle.

X

No

After 6B Open?

N/A

X

Yes

Yes

Determines door movement open or close, after 6B.

X

No

61 Monitoring

N/A

X

Active

X

Not Active

Not Active

Sensor monitoring function *

62 Monitoring

N/A

X

Active

X

Not Active

Not Active

Sensor monitoring function *

6B Monitoring

N/A

X

Active

X

Not Active

Not Active

Sensor monitoring function *

SWL Monitoring

N/A

X

Active

X

Not Active

Not Active

Sensor monitoring function *

* If Monitoring is enabled for any input then the sensor MUST be connected to Output 1 or 2.

Output 1 or 2 must then be programmed to “Sensor Health Check”. If an error occurs, the door will

hold open until the error clears or the power is cycled.

Summary of Contents for Opus Control

Page 1: ...HAPTER 1 SAFETY 2 CHAPTER 2 SCOPE 3 SECTION 2 1 To the Installer 3 SECTION 2 2 Objective 3 CHAPTER 3 FEATURES 3 CHAPTER 4 SPECIFICATIONS 3 SECTION 4 1 General Specifications 3 SECTION 4 2 Electrical S...

Page 2: ...esult in seriouc personal or fatal injury When uncertain whether power supply is disconnected always verify using a voltmeter Do not place finger or uninsulated tools inside the electrical controller...

Page 3: ...nd Folding Doors X X Existing swing and folding doors using Analog Magnum or U01 U19 controls works with encoders or microswitches X X Existing sliding doors using U01 U19 controls Retrofit kits can b...

Page 4: ...er 24 VAC P N A 01185 The Opus Control must Not be used to output power to X X Magnetic Locks X X Electric Strikes To determine if an auxiliary power supply must be used add the total current draw of...

Page 5: ...of Header End Cap Attention Electrical circuit to Nabco operator must not be not shared with other equipment such as lighting cash registers or any device that might cause electrical interference on t...

Page 6: ...Communication 7 CN1 Power Connector 4 Rotary Dial 8 Fuse CHAPTER 7 THE ROTARY DIAL X X Push down on the Rotary Dial Long push 2 seconds to gain access to LCD Catagory Screens Short push under 2 second...

Page 7: ...lose Recycle Cnt Latest Recycle Posi on DN 1334 LEVEL 4 Push and Hold Rotary Dial 2 Sec Rotate Dial Rotate Dial Rotate Dial Short Push Figure 3 LCD Screen Transition SECTION 8 1 Level One Specificatio...

Page 8: ...oke Learning Go to Se ng menu Reset to Default Set Yes No Passcode Stroke Learning Yes No Ac vate Passcode Rotate Dial Rotate Dial Rotate Dial Figure 6 Level Two Screen Attention To prevent tampering...

Page 9: ...oints should happen Stroke Learning is also used to determine if an existing Operator Type is correct and or to determine if Handing is correct 1 Briefly press down on the Rotary Dial to select X X Ye...

Page 10: ...ly Open X X Slide Door 1 to 13 3 4 of Fully Open Close Speed 0 7 3 The higher the number the faster the Door closes Latch Check Speed 0 7 3 Sets door speed during latch check Latch Check Range 0 7 3 X...

Page 11: ...essure Manual Open Function No Action No Action Does nothing Push and Go P G Enables push and go Stop and Close S C Door pauses at open angle then closes Open Assist X X Assisted Power from motor when...

Page 12: ...X X Sensor Monitoring N C X X BEA Bodyguard Output Full Open X X Output doesn t change state X X Output changes when fully closed X X Output changes when door is closing X X Output changes when door...

Page 13: ...e to reduced open Emergency Close Forces the door to slowly close and lock if equipped Hold Open Mode Causes the door to hold open forever Input H Open Timer N A Same as Open Timer 0 thru 10 12 15 20...

Page 14: ...or slide doors it displays the position in inches from closed Test Open Tests Open Close door cycle while ignoring Safety Signals CHAPTER 9 COMMON PROGRAM ADJUSTMENTS SECTION 9 1 Stroke Learning UNIT...

Page 15: ...PECS Passcode Go to Se ng menu Stroke Learning Yes No Push and Hold Rotary Dial 2 Sec LEVEL 1 LEVEL 2 1 Rotate Dial to select Go to Se ng menu 2 Push Rotary Dial Se ng Category LEVEL 3 History Se ng P...

Page 16: ...Sequential activation Signal to open Signal to close 10 H Programmable input 11 M0 Mode 0 When grounded puts door into One Way Mode Hold Open when grounded with M1 12 M1 Mode 1 When grounded puts door...

Page 17: ...17 of 32 www NabcoEntrances com Opus Control Wiring and Programming Installation Manual Rev 10 20 17 P N C 00139 SECTION 10 2 Switches and Sensors with Monitoring DN 1895...

Page 18: ...ces Non Powered Activation Devices WARNING Total Power Consumption Of All Sensors And Powered Activation Devices Must Not Exceed 750 mA 7 6 5 4 3 2 1 3 2 4 All Device Outputs Must Be N O Dry Contact 7...

Page 19: ...3 2 1 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Exterior Push Plate Interior Push Plate COM N O COM N O All Devices Must Be N O Dry Contact Powered Activation Devices sensor card reader radio receiver etc Powe...

Page 20: ...or Slide Door Sidelite Sensor 7 Out1 Programmable Output 14 13 12 11 10 9 8 7 6 5 4 3 2 1 7 6 5 4 3 2 1 2 4 COM N O PWR PWR 1 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor CO O PWR...

Page 21: ...com Opus Control Wiring and Programming Installation Manual Rev 10 20 17 P N C 00139 SECTION 11 4 Safety with Monitoring Door Mounted Swing Side Sensor Door Mounted Approach Side Sensor Overhead Swing...

Page 22: ...4 13 12 11 10 9 8 7 6 5 4 3 2 1 Fail Secure Electric Strike Fail Secure Lock Shown Fail Safe and Mag Locks will use N C instead of N O Power Supply For Electric Strike N O COM N C Varistor MOV TVS DO...

Page 23: ...G TOTAL POWER CONSUMPTI ON OR ALL SENSORS MUST NOT EXCEED 750 mA ON OFF Hold Open Switch P N A 00805 COM N O PWR PWR COM N O PWR PWR COM N O PWR PWR COM N O PWR PWR va on Sensor Overhead Swing Side Se...

Page 24: ...24 of 32 Opus Control Wiring and Programming Installation Manual www NabcoEntrances com P N C 00139 Rev 10 20 17 SECTION 11 7 Single Full Automatic with Monitoring DN 1658...

Page 25: ...N O PWR PWR 1 RED BLUE BLACK 14 13 12 11 10 9 8 8 WHITE 14 13 12 11 10 9 8 7 6 5 4 3 2 1 6 4 5 COM N O PWR PWR Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor COM N O PWR PWR COM N O...

Page 26: ...26 of 32 Opus Control Wiring and Programming Installation Manual www NabcoEntrances com P N C 00139 Rev 10 20 17 SECTION 11 9 Simultaneous Pair Full Automatic with Monitoring DN 1660...

Page 27: ...430 Clear A 70430 Dark Bronze RED BLACK 14 13 12 11 10 9 8 8 WHITE Off Hold Open On Off 14 13 12 11 10 9 8 8 14 BA break out input must be set to N C on the Opus Control is by default Panic Latch must...

Page 28: ...r connecting to a second Opus for Sim Pair Astragal Sequencing 14 13 12 11 10 9 8 10 14 Example of a switch being used to turn on off Power Close and Hold Closed Programmable input H terminal 10 would...

Page 29: ...irm that IN or EXT highlights when an activation signal isapplied If not check the wiring or the activation device X X At the main screen determine if BA is highlighted If a 4 wire on off hold openswi...

Page 30: ...he Opus will stop door movement Possible causes are X X Abnormal voltage at Motor Circuit X X Abnormal current draw from motor X X Check all connections between the Control and Motor X X Check Motor F...

Page 31: ...00888 CONTROLLER OPUS W CHASSIS BRAKE 9 M 01072 HARNESS POWER MAGNUM BOARD 10 V 00713 Used on A 01249 FUSE 2 AMP 5X20MM 250V FAST ACTING 11 A 01249 Used on GT710 8710 only HARNESS MOTOR OPUS 710 12 A...

Page 32: ...T 10 7 M 01680 HARNESS OPUS CONTROL SIM PAIR 8 A 01098 CONTROLLER W BRAKE BOTTOM LOAD OPUS 9 M 01735 PLATE BOTTOM LOAD OPUS 10 A 01143 CONTROLLER W O BRAKE BOTTOM LOAD OPUS 11 A 01003 Not used on GT71...

Reviews: