
Adjustments and Status LEDs
4-11
Rev. 9-09-16
Part #C-00084
Magnum 4A Control Wiring and Adjustment Manual
Figure 4-3
Dip Switch
(Displayed in ON position)
DN 0561
OFF
SWITCHES SHOWN IN “ON” POSITION
1 Not Used
2 OFF: Closed Loop Safety / ON: Open Loop Safety
3 OFF: Push-N-Go active / ON: Push-N-Go Inactive
4 OFF: Sequential Mode / ON: Timer Mode
Table 4-1
Dip Switch Settings
Switch
Adjustment
1
Not Used
2
On Open Loop Safety
X
Safety triggered when contact is closed by a Switch or Sensor
Off
Closed Loop Safety (Fail Safe)
X
* Safety triggered when contact is opened by a Switch or Sensor
3
On
Push-N-Go Inactive
X
Push-N-Go is not active
Off
Push-N-Go Active
X
GT710 and swingers with clutchless operators: Push-N-Go is
active in any position.
X
GT300/400/500 Swingers with clutched operator: Push-N-Go is
only active when door is pushed out of latch check.
X
Door opens when pushed.
• Switch 4 must be turned “On” for door to time out and close.
4
On Timer Mode
X
Door will open, time out and then close.
Off Sequential Mode
X
One activation opens door, second activation closes door.
* Door will not work if dipswitch 2 is OFF without a closed circuit between terminals 5 & 4 and 5 & 3. The Red LED
will also blink.
4.b.b: The Slide Switch (SW2)
The Slide Switch is used to select Operator mode during motor operation. These two modes are:
►
►
Upper Position
• Used for Low Energy Operators.
• Motor power is reduced to approximate ANSI 156.19 Low Energy Standards.
►
►
Lower Position
• Used for Standard Full Automatic Operators.
•
Can also be used for GT-500 or GT-710 if opening speed of door needs to be increased.
• Motor power is increased to approximate ANSI 156.10 Standards.
It is recommended to set door speeds as slow as the owner will accept, and no more than the applicable
ANSI Standards. Use a stopwatch for assistance. Please see
4.b.c: Potentiometers (1-8)
Note: Each Potentiometer is adjusted to meet field requirements.
There are (8) Potentiometers located on the Magnum 4A Control. Use a small #0 Cross Point or Phillips
screwdriver to adjust each potentiometer by turning it:.
►
►
Clockwise to
increase
a parameter.
►
►
Counterclockwise to
decrease
a parameter.