A
Technical Specifications
Model
Items
NE20L/NE20PL
NE30L/NE30PL
Voltage range (Vac)
208V
Rectifier input frequency
range (Hz)
50/60±10%
Bypass
synchronization
tracking range (Hz)
50/60±5%
(
±10% optional
)
Bypass input voltage range
(V)
+20%/+15%/-15%/-20%/-25%
Input power factor (PF)
>
0.99
Input current harmonic
(THDI)
<3%
Phase
3
φ
4W+PE
Battery voltage (Vdc)
167
~
224
Input
Charging current (A)
Can be set from 1 to 10.
Power
20kVA/18kW
30kVA/27kW
Phase
3
φ
4W+PE
Output wave-form
Sine wave
Voltage (Vac)
208±1%
Output
Frequency (Hz)
If bypass is normal, it will track automatically and synchronously; if bypass
failure the frequency is 50/60±0.1 of the UPS.