Not Available on CE Rated Systems.
A GFCI is an important safety device and is required equipment on a hot tub installation.
Your spa may be equipped with a GFCI Protection feature. (UL rated systems only.) If your spa has this feature enabled by
the manufacturer, the GFCI Trip Test must occur to allow proper spa function.
Within 1 to 7 days after startup, the spa will trip the GFCI to test it. (The number of days is factory programmed.) The GFCI
must be reset once it has tripped. After passing the GFCI Trip Test, any subsequent GFCI trips will indicate a ground fault or
other unsafe condition and the power to the spa must be shut off until a service person can correct the problem.
Forcing the GFCI Trip Test
The installer can cause the GFCI Trip Test to occur sooner by initiating it using the above menu.
The GFCI should trip within several seconds and the spa should shut down. If it does not, shut down the power and manu-
ally verify that a GFCI breaker is installed and that the circuit and spa are wired correctly. Verify the function of the GFCI
with its own test button. Restore power to the spa and repeat the GFCI Trip Test.
Once the GFCI is tripped by the test, reset the GFCI and the spa will operate normally from that point. You can verify a suc-
cessful test by navigating to the above menu. PASS should appear after a temp button is pressed from the GFCI screen.
The end-user must be trained to expect this one-time test to occur and how to properly reset the GFCI.
Warning:
If freezing conditions exist, a GFCI should be reset immediately or spa damage
could result. The end user should always trained to test and reset the
GFCI on a regular basis.
Utilities – GFCI Test Feature
Only if GFCI
is enabled
To FIRST item in
Main Menu
(TEMP Range)
To next item in
Info Menu
(A/B°)
Only appears
if a GFCI test
has been
passed.
While the Temperature is
still flashing, press Light
repeatedly until UTIL (Utilities)
appears in the LCD.
TRIP may also
appear briefly
under certain
circumstances.
One of these screens
will appear.
If the GFCI does
NOT trip, FAIL will
appear and Spa
will not operate.
The GFCI will be tripped
at a random interval.
When the GFCI trips,
the spa will shut down.
After the breaker is
reset, PASS will
appear in this menu
and the spa will
operate normally.
SET
RANGE
Main Screen
READY
RANGE FLTR1
SET
Waiting several seconds inside the GFCI Menu will allow the screen to return to normal operation.
*****
Or Wait to
Revert
*****
Or Wait to
Revert
*****
Or Wait to
Revert
*****
Indicates Flashing or Changing Segment
Key
A temperature button, used for “Action”
Light or dedicated “Choose” button, depending on control panel configuration
Indicates Alternating or Progressive Message - every 1/2 second
Waiting time that keeps the last change to a menu item.
Waiting time (depends on menu item) that reverts to original setting and
ignores any change to that menu item.
*****
Indicates a Menu Item that
Depends on a Manufacturer
Configuration and
may or may not appear.
Not Available on CE Rated Systems.
A GFCI is an important safety device and is required equipment on a hot tub installation.
Your spa may be equipped with a GFCI Protection feature. (UL rated systems only.) If your spa has this feature enabled by
the manufacturer, the GFCI Trip Test must occur to allow proper spa function.
Within 1 to 7 days after startup, the spa will trip the GFCI to test it. (The number of days is factory programmed.) The GFCI
must be reset once it has tripped. After passing the GFCI Trip Test, any subsequent GFCI trips will indicate a ground fault or
other unsafe condition and the power to the spa must be shut off until a service person can correct the problem.
Forcing the GFCI Trip Test
The installer can cause the GFCI Trip Test to occur sooner by initiating it using the above menu.
The GFCI should trip within several seconds and the spa should shut down. If it does not, shut down the power and manu-
ally verify that a GFCI breaker is installed and that the circuit and spa are wired correctly. Verify the function of the GFCI
with its own test button. Restore power to the spa and repeat the GFCI Trip Test.
Once the GFCI is tripped by the test, reset the GFCI and the spa will operate normally from that point. You can verify a suc-
cessful test by navigating to the above menu. PASS should appear after a temp button is pressed from the GFCI screen.
The end-user must be trained to expect this one-time test to occur and how to properly reset the GFCI.
Warning:
If freezing conditions exist, a GFCI should be reset immediately or spa damage
could result. The end user should always trained to test and reset the
GFCI on a regular basis.
Utilities – GFCI Test Feature
Only if GFCI
is enabled
To FIRST item in
Main Menu
(TEMP Range)
To next item in
Info Menu
(A/B°)
Only appears
if a GFCI test
has been
passed.
While the Temperature is
still flashing, press Light
repeatedly until UTIL (Utilities)
appears in the LCD.
TRIP may also
appear briefly
under certain
circumstances.
One of these screens
will appear.
If the GFCI does
NOT trip, FAIL will
appear and Spa
will not operate.
The GFCI will be tripped
at a random interval.
When the GFCI trips,
the spa will shut down.
After the breaker is
reset, PASS will
appear in this menu
and the spa will
operate normally.
SET
RANGE
Main Screen
READY
RANGE FLTR1
SET
Waiting several seconds inside the GFCI Menu will allow the screen to return to normal operation.
*****
Or Wait to
Revert
*****
Or Wait to
Revert
*****
Or Wait to
Revert
*****
Indicates Flashing or Changing Segment
Key
A temperature button, used for “Action”
Light or dedicated “Choose” button, depending on control panel configuration
Indicates Alternating or Progressive Message - every 1/2 second
Waiting time that keeps the last change to a menu item.
Waiting time (depends on menu item) that reverts to original setting and
ignores any change to that menu item.
*****
Indicates a Menu Item that
Depends on a Manufacturer
Configuration and
may or may not appear.
Not Available on CE Rated Systems.
A GFCI is an important safety device and is required equipment on a hot tub installation.
Your spa may be equipped with a GFCI Protection feature. (UL rated systems only.) If your spa has this feature enabled by
the manufacturer, the GFCI Trip Test must occur to allow proper spa function.
Within 1 to 7 days after startup, the spa will trip the GFCI to test it. (The number of days is factory programmed.) The GFCI
must be reset once it has tripped. After passing the GFCI Trip Test, any subsequent GFCI trips will indicate a ground fault or
other unsafe condition and the power to the spa must be shut off until a service person can correct the problem.
Forcing the GFCI Trip Test
The installer can cause the GFCI Trip Test to occur sooner by initiating it using the above menu.
The GFCI should trip within several seconds and the spa should shut down. If it does not, shut down the power and manu-
ally verify that a GFCI breaker is installed and that the circuit and spa are wired correctly. Verify the function of the GFCI
with its own test button. Restore power to the spa and repeat the GFCI Trip Test.
Once the GFCI is tripped by the test, reset the GFCI and the spa will operate normally from that point. You can verify a suc-
cessful test by navigating to the above menu. PASS should appear after a temp button is pressed from the GFCI screen.
The end-user must be trained to expect this one-time test to occur and how to properly reset the GFCI.
Warning:
If freezing conditions exist, a GFCI should be reset immediately or spa damage
could result. The end user should always trained to test and reset the
GFCI on a regular basis.
Utilities – GFCI Test Feature
Only if GFCI
is enabled
To FIRST item in
Main Menu
(TEMP Range)
To next item in
Info Menu
(A/B°)
Only appears
if a GFCI test
has been
passed.
While the Temperature is
still flashing, press Light
repeatedly until UTIL (Utilities)
appears in the LCD.
TRIP may also
appear briefly
under certain
circumstances.
One of these screens
will appear.
If the GFCI does
NOT trip, FAIL will
appear and Spa
will not operate.
The GFCI will be tripped
at a random interval.
When the GFCI trips,
the spa will shut down.
After the breaker is
reset, PASS will
appear in this menu
and the spa will
operate normally.
SET
RANGE
Main Screen
READY
RANGE FLTR1
SET
Waiting several seconds inside the GFCI Menu will allow the screen to return to normal operation.
*****
Or Wait to
Revert
*****
Or Wait to
Revert
*****
Or Wait to
Revert
*****
Indicates Flashing or Changing Segment
Key
A temperature button, used for “Action”
Light or dedicated “Choose” button, depending on control panel configuration
Indicates Alternating or Progressive Message - every 1/2 second
Waiting time that keeps the last change to a menu item.
Waiting time (depends on menu item) that reverts to original setting and
ignores any change to that menu item.
*****
Indicates a Menu Item that
Depends on a Manufacturer
Configuration and
may or may not appear.
Adjusting the Set Temperature
When using a panel with Up and Down buttons (Temperature buttons), pressing Up or Down will cause the temperature to
flash. Pressing a temperature button again will adjust the set temperature in the direction indicated on the button. When
the LCD stops flashing, the spa will heat to the new set temperature when required.
If the panel has a single temperature button, pressing the button will cause the temperature to flash. Pressing the button
again will cause the temperature to change in one direction (e.g. UP). After allowing the display to stop flashing, pressing
the Temperature Button will cause the temperature to flash and the next press will change the temperature in the opposite
direction (e.g. DOWN).
Press-and-Hold
If a Temperature button is pressed and held when the temperature is flashing, the temperature will continue to change
until the button is released. If only one temperature button is available and the limit of the Temperature Range is reached
when the button is being held, the progression will reverse direction.
Dual Temperature Ranges
This system incorporates two temperature range settings with independent set temperatures. The High Range designated in
the display by an “up” arrow, and the Low Range designated in the display by a “down” arrow.
These ranges can be used for various reasons, with a common use being a “ready to use” setting vs. a “vacation” setting.
The Ranges are chosen using the menu structure below. Each range maintains its own set temperature as programmed by
the user. This way, when a range is chosen, the spa will heat to the set temperature associated with that range.
For example:
High Range might be set between 80°F and 104°F.
Low Range might be set between 50°F and 99°F.
More specific Temp Ranges may be determined by
the Manufacturer.
Freeze Protection is active in either range.
See Ready and Rest on Page 6
for additional heating control information.
Temperature and Temp Range
High-Range vs.
Low-Range Temp Choice
Press a Temp Button repeatedly to change the temperature.
Pressing and holding a Temp Button will also change the temperature.
Pressing and holding a Temp Button will also change the temperature.
Toggle the Range arrows in the LCD.
SET
RANGE
SET
RANGE
Set Temp will Show & Flash
Set Temp will Show & Flash
SET
RANGE FLTR1
SET
RANGE FLTR1
SET
RANGE FLTR1
SET
RANGE
SET
RANGE
Waiting
Several Seconds
Reverts to Original Setting
To Set
*****
SET
RANGE
While
temperature
is flashing...
To next item in Main Menu
Main Screen
READY
RANGE FLTR1
Main Screen
READY
RANGE FLTR1
Several Seconds
OR
Main Screen
READY
RANGE FLTR1
Press a Temp Button repeatedly to change the temperature.
Several Seconds
OR
Main Screen
READY
RANGE FLTR1
Main Screen
READY
RANGE FLTR1
Indicates Flashing or Changing Segment
Key
A temperature button, used for “Action”
Light or dedicated “Choose” button, depending on control panel
configuration
Indicates Alternating or Progressive Message - every 1/2 second
Waiting time that keeps the last change to a menu item.
Waiting time (depends on menu item) that reverts to original
setting and ignores any change to that menu item.
*****