LCD display instruction
When inverter alarm, even it back to recovery mode. We must restart inverter to clear fault.

Fault code Fault

Fan fault

Over temperature

DC voltage too high

DC voltage too low

Output short circuit
in DC model

Output over voltage

Output over load

Output over current

Output low voltage
in DC model

Fault instruction

Fan stop run

Output short circuit: 
short circut test fault 05
Output over voltage: 
V

>135V/270V 500ms fault 06

output

overload:
100%<Load<110% alarm per every second (5min later inverter cutoff output 
and fault 07)
110%<Load<125% alarm per every second (60s later inverter cutoff output 
and fault 07)
Load>125% alarm per every second (10s later cut off output and fault 07)

Inverter Output over current: 
1-3K: I >40A.  4-6K: I >80A 200ms  fault 51

rms

rms

Output low voltage:
V

<85V/170V 500ms fault 58

output

LED/Buzzer

LCD

Explanation / Possible cause

What to do

Buzzer beeps
continuously 
and red LED 
is on

Fault code 01 Fan stop run

Check the fan.

Temperature of machine is too high. Power off and waiting for minute

Fault code 02

Fault code 03 Battery voltage is too high.

Check the battery specifications

Fault code 04 Battery voltage is too low.

Check the battery specifications

Fault code 05 Output short circuited

Remove your load and restart

Fault code 06 Inverter output voltage is high.

Fault code 07 Over load

Decrease your load

Fault code 51 Output over current

Check if wiring is connected well and remove 
abnormal load.

Fault code 58 Output voltage is too low.

Decrease your load

Return to repair center

Trouble shooting

If machine enters into fault mode, please remove input power. And according to the table, deal with the following 
problems.

BTS over temperture:

o

o

T

>65 C 1s 1 time for 1min then fault alarm 02; T

<60 C  recovery

battery

battery

Inverter over temperture:

o

o

T >90 C  1s1time for 1min then fault alarm 02; T <85 C  recovery

inv

inv

Battery over voltage:
DC>V

alarm for 30s then fault code 03

(charge 1V)/12V 

Over voltage recovery:
DC<V

  

(charge 1V)-0.2V/12V

Low voltage alarm:
DC<V

(0.5V)/12V

Alarm recovery:
DC>V

 

(0.5)+0.2/12V

Low voltage fault:
DC<V

  fault code 04

cutoff

-17-

Summary of Contents for EP33-1012TLV

Page 1: ...PC TV Air conditioning Fridge Washing machine Appliances INVERTER CHARGER 1012 1024 1512 1524 2012 2024 3024 3048 4024 4048 5048 6048...

Page 2: ...e Unit 4 Operation 8 Operation key instructions 8 Setting key instructions 8 LCD display 10 Operating mode description 11 AGS function 11 AGS function information 11 Dry contact operating voltage 12 B...

Page 3: ...tal tools around batteries Batteries short circuiting could cause an explosion 5 Read the battery installation and maintenance instructions carefully before operating Personnel Precautions 1 Better to...

Page 4: ...multi function display Overload and short circuit protection Set charging voltage charging current Battery low voltage shutdown point can be set to 10 10 5 11V Power save mode Set utility priority Bat...

Page 5: ...N AC Side Panel 1 AC OUTPUT HOT1 N 120VAC 110 VAC 115VAC 2 AC OUTPUT HOT2 N 120VAC 110 VAC 115VAC 3 AC OUTPUT HOT1 HOT2 240VAC 220 VAC 230VAC 4 AC INPUT HOT1 HOT2 240VAC 220 VAC 230VAC 5 15AMAX JFCI...

Page 6: ...Mounting the Unit Consider the following points before selecting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye le...

Page 7: ...enough or connect several combined thin cables together to be same strong Battery bank should be kept close to inverter The shorter and thicker cables the better the system performance Please follow b...

Page 8: ...ent of AC input Suggestion AC breaker 50A for 1KW 3KW 80A for 4KW 6KW CAUTION Please don t connect the output wring to Grid terminal or connect the grid wring to the Load terminal WARNING All wiring m...

Page 9: ...re required at least 2 3 minutes to restart because it s required to have enough time to balance refrigerant gas inside of circuits If a power shortage occurs and recovers in a short time it will caus...

Page 10: ...ormally set To ensure that the parameters can be successfully saved so every time after setting the parameters need restart the machine Setting key instructions MENU Function key Function description...

Page 11: ...d current default Range of adjustment 13 8 14 5V 14 1V default 17 Floating charging setting 13 5V default 10 5V default 18 Range of adjustment 13 5 13 7V 11 5V default 13 5V default 21 LCD ON LCD OFF...

Page 12: ...n switch on The Battery voltage and rated power shall be displayed on the LCD screen when switch on As this shown in Screen 3024 Default Page Output Voltage and Output Frequency Input Voltage and Inpu...

Page 13: ...function AGS function information The AGS function is that the inverter will start the generator automatically via the dry contact when the battery is low voltage Note The generator must have dry con...

Page 14: ...based on drops of boost voltage and float voltage Using an optional battery temperature cable to connect the inverter and battery Communication Upper Computer Monitoring directions Monitoring software...

Page 15: ...er Monitor exe and install Open the PowerMonitor turn on the machine Desktop shortcut Icon 13 Solar Power Monitor exe Advanced Installer SolarPowerMonitor has been successfully installed SolarPowerMon...

Page 16: ...or a moment Power Monitor will work normally Monitor software function operation Specific function Operations of the monitoring software please refering to the HELP docs after the connection is succes...

Page 17: ...0V F 65HZ AC 265V F 65HZ AC 265V F 70HZ AC 270V F 70HZ AC 270V F 45HZ AC 150V F 45HZ AC 190V F 40HZ AC 140V F 40HZ AC 180V narrow wide Charge Mode Specifications Max charge current 5A model 1K 1 5K 2K...

Page 18: ...the charger will run at full current in CC mode until the charger reaches the boost voltage Boost CV Stage the charger will keep the boost voltage in Boost CV mode until the charge current less 6A con...

Page 19: ...Temperature of machine is too high Power off and waiting for minute Fault code 02 Fault code 03 Battery voltage is too high Check the battery specifications Fault code 04 Battery voltage is too low C...

Page 20: ...420 00341 02 INVERTER CHARGER...

Reviews: