General data
User manual 57120_hdb_en_12
19 / 70
*) Due to single high-energy impulses, a suitable external wiring with light-
ning protection elements is required for surge, e.g. lightning arresters and
surge arresters.
EMC / standards
Remarks
Emitted interfer-
ence
EN 61000-6-4
Class A (industrial environments)
Immunity Zone B EN 61000-6-2
Industrial environments
EN 61000-4-2
ESD
8 kV with air discharge (severity grade 3),
4 kV with contact discharge (severity grade 2)
EN 61000-4-3
HF irradiation (housing)
80 MHz ... 1000 MHz, 10 V/m, 80 % AM (1 kHz)
1.4 GHz ... 2.0 GHz, 3 V/m, 80 % AM (1 kHz)
2 GHz ... 2.7 GHz, 1 V/m, 80 % AM (1 kHz)
EN 61000-4-6
conducted 150 kHz … 80 MHz,
10 V, 80 % AM (1 kHz)
EN 61000-4-4
Burst, severity grade 3
EN 61000-4-5
Surge, installation class 3 *)