Power modules
User manual 57120_hdb_en_12
62 / 70
Tab. 10-3: Assignment of connecting terminals
10.3.3
Supply
NOTE
Power and electronics supply are protected internally by fuses against high
voltages. The fuses are located inside the power module.
After a fuse has tripped, the electronic module of the power module has to
be replaced!
Power module art. no.
57131
Fuse protection of the power module electronics supply of the I/O level
Fuse-protect the electronics supply externally!
Use:
A 1 A fuse (fast)
or
a 1 A circuit breaker of characteristic Z
or
MICO load circuit monitoring,
e.g. MICO 4.4, Art.-No. 9000-41034-0100400
External fuse
To protect the power supply, Murrelektronik provides a number of circuit break-
ers. They can be found under the product name
MICO
on the internet
www.murrelektronik.com.
NOTICE
Voltage supply interruptions!
The module does not have any internal buffer to bridge voltage supply inter-
ruption according to the standard EN 61131-2.
For power supply use a power supply unit which is capable of bridging volt-
age supply interruptions of at least 10 ms!
NOTICE
Exceeding of the maximum current load!
The contacts can be loaded with maximum 10 A.
Observe the maximum current load!
10.3.4
Using
Use
The standard wiring of the power supply in combination with the bus node is
Pos. Function
Type
Description
1
---
---
not used
2
24 V DC
Input
Supply of 24 V DC power supply
3
0 V
Input
Supply of ground GND power supply
4
Sys 24 V DC
Input
Supply of 24 V DC electronics supply
5
---
---
not used
6
24 V DC
Output
24 V DC power supply of I/Os
7
0 V
Output
Ground GND power supply of I/Os
8
0V
Input
Supply of ground GND electronics supply