background image

3-2  MC-900.
3-2.1  

Control / Display Module.  The Control / Display

Module, figure 3-2.1, includes the control and test switches,
the solid state logic elements and shutdown TATTLETALE

®

lights that make up the generator engine control for a four
cycle engine.

3-2.1.1  

Mode Selector Switch, OFF-RUN-START:

(a)  OFF; turns off the control system and resets any

shutdown circuits.

(b)  RUN; turns on the engine controls and shutdown

circuits.  System is on, waiting for the engine to start.
Switch returns to run position from START after starting
engine.

(c)  START; turns on the engine start circuit.  A start signal is

applied to the auxiliary start solenoid and the engine
starter engages.  Releasing the start switch disconnects
cranking.

3-2.1.2  

Lamp Test Pushbutton: Tests the lights on the MC-900

module when the Mode Selector Switch is in the RUN
position.

3-2.1.3  

The MC-900 SELECTRONIC

®

Control Module

includes the following engine control features: 

(a)  Overcrank circuit;  will stop manual cranking and

indicate overcrank if start switch remains closed longer
than the overcrank time setting.  The crank time is
selectable for 10, 15, 20, 25 or 30 seconds before
shutdown.

(b)  Shutdown Time Delay Bypass;  this delay prevents the

oil pressure and water temperature shutdown circuits
from operating for 30 seconds after the engine starts as
detected by the Mode Selector Switch returning to RUN

position.  This same delay can also lock out all other
shutdown circuits except Overspeed and Overcrank.
The user may select which circuits are locked out by the
time delay bypass.

(c)  Overspeed Speed Switch;

1.  Provides a signal to the overspeed shutdown circuit

if the engine exceeds the preset speed.  The factory
setting is approximately 3894 Hz, or 1980 RPM on
an engine with 118 teeth on the flywheel ring gear.
The adjustment range is 300 Hz to 10,000 Hz.

2.  A push to test switch is provided to allow testing of

the overspeed circuit without overspeeding the
engine.  When switch is depressed, the set point of
the speed switch is lowered approximately 10%.

3.  The push to test switch can also be used to set the

overspeed switch at approximately 110% of running
speed. Hold the switch depressed while adjusting the
setting until the overspeed trips.  When switch is
released, the set point will be 10% above normal
running speed.  This is the method used to make the
factory setting.  With engine speed at 1800 RPM or
3540 Hz.

3-2.1.4  

Eight (8) First-out Shutdown Circuits;  provide first-

out indication of cause of shutdown.  These circuits deactivate
the fuel relay and lockout the MC-900 until reset. Shutdown
circuits are activated by the Mode Selector Switch and or
Shutdown Time Delay Bypass.  Eight (8) Red Shutdown
Indicating Lights are provided.

(a)  Overcrank;  tripped by the overcrank timing circuit

which times as long as the START switch is closed.

(b)  Overspeed;  tripped by overspeed switch when engine

exceeds a preset speed.

(c)  Oil Pressure;  tripped by the oil pressure SWICHGAGE

®

if pressure drops below preset point while the engine is
running.

(d)  Water Temperature;  tripped by the water temperature

SWICHGAGE

®

if engine coolant temperature exceeds

the switch setting.

(e)  Spare Shutdowns;  tripped by an external switch.  These

circuits are provided for additional shutdowns that may
be recommended by the engine supplier or required by
the user.

3-2.2  

Relay Module.  The Relay Module, figure 3-2.2,

includes all of the control and shutdown relays that are
required to make up the generator engine control.  Relays are
available for operation on either 12 or 24 volt battery systems.
Two (2) relays are included for:

3-2.2.1  

Fuel Relay;  this relay provides two outputs, one to

energize the engine fuel solenoid and a separate circuit to
energize the battery charging alternator field.

3-2.2.2  

Shutdown Relay;  this relay is operated by the

shutdown circuits of the Control / Display Module and
provides an output that can be used to trip the generator circuit
breaker on an emergency shutdown.

3-2.3 

Status Signal;  The relay module also includes an output

that can be used with external circuits for signaling or control
functions.

3-2.3.1  

The Run signal at terminal 17 is on (closed to

negative) as long as the Mode Selector Switch is in either Run

2

Overcrank

OFF 

RUN

START

Lamp Test

Water

Temperature

Oil Pressure

6-15/32 in.

(164 mm)

9-3/4 in.

(248 mm)

Overspeed

Figure 3-2.1

Summary of Contents for MURPHYMATIC MC-900 Series

Page 1: ...SERIES MC 900 MURPHYMATIC MANUAL GENERATOR ENGINE CONTROL SYSTEM DESIGN INSTALLATION AND OPERATING MANUAL MC 9142N Revised 12 00 Section 40 00 02 0202 ...

Page 2: ...1 Model Numbers 1 3 2 MC 900 2 3 3 MC 900 2 3 Section 4 Installation 3 4 1 Location 3 4 2 Wiring 3 4 3 Overspeed Switch 7 4 4 Pre Operational Check Out 7 Section 5 Operation 8 5 1 Operator Controls 8 5 2 Operating Modes 8 Section 6 Routine Maintenance and Operational Tests 8 6 1 Routine Maintenance 8 6 2 Operational Tests 8 Section 7 Troubleshooting and Repair 8 7 1 Tools Required 8 7 2 MC 900 SEL...

Page 3: ...ures in detail Section 2 Specifications 2 1 Enclosure Type 2 1 1 The MC 900 Series enclosure is designed to be mounted in a standard electrical enclosure for indoor use 2 1 2 The MC 900 Series shares the same enclosure as the A 900 automatic start controller so they can be used interchangeably in a generator control panel 2 2 Power Requirements 2 2 1 The engine controls shutdown circuits and shut ...

Page 4: ...be used to set the overspeed switch at approximately 110 of running speed Hold the switch depressed while adjusting the setting until the overspeed trips When switch is released the set point will be 10 above normal running speed This is the method used to make the factory setting With engine speed at 1800 RPM or 3540 Hz 3 2 1 4 Eight 8 First out Shutdown Circuits provide first out indication of c...

Page 5: ...minals Terminal blocks are provided on both sides of the Control Display enclosure and the Relay Module Torque all terminal screws to 12 inch pound maximum 4 2 Wiring 4 2 1 After the MC 900 has been located and installed the wiring connections can be made This work should be done with all electrical power disconnected from the engine BE SURE THAT THE BATTERY IS DISCONNECTED 4 2 2 All electrical in...

Page 6: ...6 mm 6 3 4 in 171 mm 9 3 8 in 238 mm 6 in 152 mm 4 15 32 in 114 mm Mounting Holes 1 8 in 3 mm diameter 5 in 127 mm maximum between MC 900 and relay module 1 7 8 in 48 mm clearance 1 1 2 in 38 mm clearance 1 1 2 in 38 mm clearance 1 7 8 in 48 mm clearance NOTE Clearance required for wire run Figure 4 1 2 Dimensions ...

Page 7: ...1 22 23 24 25 Over Speed Relay Shut Down Relay Fuel Relay J1 J2 A J2 B J2 C J2 B B FUEL RELAY SHUTDOWN RELAY OVERSPEED RELAY CRANK SIGNAL RUN SIGNAL B B to aux starter solenoid Run signal switched B MANUAL START MODULE Output Barrier Terminal Blocks Input Barrier Terminal Blocks Battery Starter Auxiliary Starter Solenoid B Ground FR Energize to Stop solenoid FR Energize to Run solenoid Fuel relay ...

Page 8: ... D E 4 5 6 7 8 9 10 11 12 13 14 3A Fuse 15 4 16 17 18 19 20 21 22 23 24 25 Over Speed Relay Shut Down Relay Fuel Relay J1 J2 A J2 B J2 C J2 B B FUEL RELAY SHUTDOWN RELAY OVERSPEED RELAY CRANK SIGNAL RUN SIGNAL B B to aux starter solenoid Run signal switched B Battery Starter Auxiliary Starter Solenoid Fuel Pressure B Ground FR Energize to Stop solenoid FR Energize to Run solenoid Fuel relay N C dr...

Page 9: ...ing using the following formulas Refer to Table 4 4 1 to determine if the speed switch setting is below the factory setting listed If required frequency will be higher than the standard increase the setting before proceeding Turn the Overspeed Set pot clockwise to increase setting The adjustment is a 20 turn control without stops at either end 4 4 1 1 Be sure to have a fully charged battery to do ...

Page 10: ... not locked out may be tested as soon as the engine is running or may be tested without starting the engine by turning the Mode Selector switch to RUN position c To test other shutdowns a jumper wire can be used to short the input terminal for that circuit to ground terminal 4 Section 5 Operation 5 1 Operator Controls 5 1 1 Mode Selector Switch allows the operator to start the engine START run the...

Page 11: ...n engine run signal closes to ground at terminal 17 when the Mode Selector switch is in the RUN position and the engine is not shutdown by the MC 900 shutdown circuits 7 2 3 With the Mode Selector switch in the RUN position six of the eight shutdown TATTLETALE circuits are activated and will operate anytime a switch closes from ground to their inputs Circuit Input Output a Oil Pressure Terminal 28...

Page 12: ...5 7 5 0 0 29 0 0 7 5 7 5 7 5 7 5 7 5 7 5 30 0 0 7 5 7 5 7 5 7 5 7 5 7 5 31 0 0 7 5 7 5 7 5 7 5 7 5 7 5 32 0 0 7 5 7 5 7 5 7 5 7 5 7 5 33 0 0 7 5 7 5 7 5 7 5 7 5 7 5 34 0 0 0 0 0 0 0 0 35 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 36 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 37 2 13 8 27 6 13 8 27 6 13 8 27 6 0 0 38 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 39 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 40 13...

Page 13: ...Relay Qty Module 2 2 3 Model Number MC 900 2 24 Waukesha Part Number 40 35 0047 Control Display 40 00 0223 Relay Module 40 00 0224 Relay Part 00 00 2953 Relay Qty Module 2 Table 8 1 Table 8 2 CONTROL SYSTEMS SERVICES DIVISION P O Box 1819 Rosenberg Texas 77471 USA 1 281 633 4500 fax 1 281 633 4588 e mail sales fwmurphy com MURPHY DE MEXICO S A DE C V Blvd Antonio Rocha Cordero 300 Fracción del Agu...

Reviews: