background image

8

been adjusted for proper running speed, turn Mode
Selector switch OFF.

(e)  All lights on the back of the MC-900 should go off and

the engine stop.  If engine does not stop, check run
solenoid to be sure it has returned to the stop position.

4-4.3  

Overspeed Switch Setting; To set the speed switch,

proceed as follows:

(a)  Turn Mode Selector switch to the START position.
(b)  Engine should crank and start.  Return switch to RUN

position.

(c)  With engine running, adjust governor to bring engine

speed to normal RPM.

(d)  Depress and hold the Overspeed Test pushbutton.
(e)  Slowly turn the Overspeed Set adjustment counter-

clockwise until the “Overspeed” and “Overspeed Relay”
lights on the MC-900 come on and the engine shuts
down.

(f)  Release pushbutton;  check “Overspeed” light on front

panel to be sure it is on.

(g)  Turn Mode Selector switch OFF to reset shutdown

circuits.

(h)  Restart engine, when engine starts, increase governor

speed setting slowly until engine shuts down on
overspeed.  This should occur about 10% above
governor speed.

(i)  Turn Mode Selector switch OFF.

4-4.4 

Overcrank setting; to test the time before system shuts

down on overcrank;

(a)  Disconnect the run solenoid wire from terminal 6 of the

Relay Module.

(b)  Check time set on the “Crank Time” switch on MC-900

back panel.  It is factory set at 15.

(c)  Turn Mode Selector switch to START.

1.  Engine will crank for 15 seconds.
2.  After 15 seconds the “Overcrank” light on the MC-

900 will come on and engine will stop cranking.

(d)  Turn Mode Selector switch OFF.
(e)  Reconnect the run solenoid wire at terminal 6 of the

Relay Module.

4-4.5 

Oil Pressure;  to test oil pressure shutdown circuit:

(a)  Turn Mode Selector switch to START.  When engine

starts, wait 30 seconds then,

(b)  Use a jumper wire and short from terminal 28 to 4.
(c)  ”Oil Pressure” light will come on and engine will stop.
(d)  Turn Mode Selector switch OFF.

4-4.6

Water Temperature;  to test the water temperature

shutdown circuit:

(a)  Turn Mode Selector switch to START.  When engine

starts, wait 30 seconds then,

(b)  Use a jumper wire and short from terminal 29 to 4.
(c)  “Water Temperature” light will come on and engine will

stop.

(d)  Turn Mode Selector switch OFF.

4-4.7

All other Shutdowns;  all other shutdowns would be

tested in the same manner.

(a)  For shutdown circuits which are locked out by the

Shutdown Time Delay Bypass, you must wait 30
seconds before running the test.

(b)  Circuits that are not locked out may be tested as soon as

the engine is running or may be tested without starting

the engine by turning the Mode Selector switch to RUN
position.

(c)  To test other shutdowns, a jumper wire can be used to short

the input terminal for that circuit, to ground, terminal 4.

Section 5: Operation

5-1  Operator Controls.
5-1.1  

Mode Selector Switch;  allows the operator to start the

engine (START), run the engine (RUN), or stop the engine
(OFF).

5-1.2

The OFF position on the mode selector also provides a

reset function for the shutdown circuits.  If the engine is shut
down by the automatic control, the operator must turn selector
off and back on to reactivate the system.

5-1.3

Push to Test Lamps;  this pushbutton tests the shutdown

indicator lights.

5-2  Operating Modes.
5-2.1 

The MC-900 Generator Engine Control has only one

operating mode: manual start and automatic shutdown on a
sensed failure of one of the monitored inputs.

5-2.2  

Manual electric start is provided for operation of the

generator set.

5-2.2.1  

To initiate Manual start, place the Mode Selector

switch in the START position.  This provides a start signal to
the engine starter.

5-2.2.2 

When engine starts, return selector switch to RUN.

This removes start signal and the engine will run.

5-2.3 

OFF or Not Operating; to prevent operation of the

engine, turn selector switch OFF.

5-2.3.1  

The OFF position is used as a reset for any automatic

shutdown that occurs.

Section 6: Routine Maintenance 

and Operational Tests

6-1 Routine Maintenance.
6-1.1

Due to the design and types of components used, very

little maintenance is required to the MC-900 Control.

6-1.2 

Visual inspection of the internal wiring of the control

panel, along with checking wire connections for tightness,
should be done on a semiannual schedule for stand- by systems
or quarterly for prime power.  Check wire bundles for chafing
and wear to the insulation of the wires where they contact the
panel or engine.

6-1.4  

Shutdown Circuits should be tested on a monthly basis

for prime power and quarterly for stand-by sets.  The same
tests run during pre-operation check out, Section 4-4, should
be included.

6-2  Operational Tests.
6-2.1

No special operational tests are required.  The routine

operational tests for the generator set will exercise the control.

Section 7: Troubleshooting and Repair

7-1  Tools Required.
7-1.1 

Some of the tools necessary for troubleshooting are built

into the MC-900 Series controls.

7-1.1.1

By observing the lights on the front and rear of the

control panel, clues to a problem and the possible source can
be seen.

Summary of Contents for MURPHYMATIC MC-900 Series

Page 1: ...SERIES MC 900 MURPHYMATIC MANUAL GENERATOR ENGINE CONTROL SYSTEM DESIGN INSTALLATION AND OPERATING MANUAL MC 9142N Revised 12 00 Section 40 00 02 0202 ...

Page 2: ...1 Model Numbers 1 3 2 MC 900 2 3 3 MC 900 2 3 Section 4 Installation 3 4 1 Location 3 4 2 Wiring 3 4 3 Overspeed Switch 7 4 4 Pre Operational Check Out 7 Section 5 Operation 8 5 1 Operator Controls 8 5 2 Operating Modes 8 Section 6 Routine Maintenance and Operational Tests 8 6 1 Routine Maintenance 8 6 2 Operational Tests 8 Section 7 Troubleshooting and Repair 8 7 1 Tools Required 8 7 2 MC 900 SEL...

Page 3: ...ures in detail Section 2 Specifications 2 1 Enclosure Type 2 1 1 The MC 900 Series enclosure is designed to be mounted in a standard electrical enclosure for indoor use 2 1 2 The MC 900 Series shares the same enclosure as the A 900 automatic start controller so they can be used interchangeably in a generator control panel 2 2 Power Requirements 2 2 1 The engine controls shutdown circuits and shut ...

Page 4: ...be used to set the overspeed switch at approximately 110 of running speed Hold the switch depressed while adjusting the setting until the overspeed trips When switch is released the set point will be 10 above normal running speed This is the method used to make the factory setting With engine speed at 1800 RPM or 3540 Hz 3 2 1 4 Eight 8 First out Shutdown Circuits provide first out indication of c...

Page 5: ...minals Terminal blocks are provided on both sides of the Control Display enclosure and the Relay Module Torque all terminal screws to 12 inch pound maximum 4 2 Wiring 4 2 1 After the MC 900 has been located and installed the wiring connections can be made This work should be done with all electrical power disconnected from the engine BE SURE THAT THE BATTERY IS DISCONNECTED 4 2 2 All electrical in...

Page 6: ...6 mm 6 3 4 in 171 mm 9 3 8 in 238 mm 6 in 152 mm 4 15 32 in 114 mm Mounting Holes 1 8 in 3 mm diameter 5 in 127 mm maximum between MC 900 and relay module 1 7 8 in 48 mm clearance 1 1 2 in 38 mm clearance 1 1 2 in 38 mm clearance 1 7 8 in 48 mm clearance NOTE Clearance required for wire run Figure 4 1 2 Dimensions ...

Page 7: ...1 22 23 24 25 Over Speed Relay Shut Down Relay Fuel Relay J1 J2 A J2 B J2 C J2 B B FUEL RELAY SHUTDOWN RELAY OVERSPEED RELAY CRANK SIGNAL RUN SIGNAL B B to aux starter solenoid Run signal switched B MANUAL START MODULE Output Barrier Terminal Blocks Input Barrier Terminal Blocks Battery Starter Auxiliary Starter Solenoid B Ground FR Energize to Stop solenoid FR Energize to Run solenoid Fuel relay ...

Page 8: ... D E 4 5 6 7 8 9 10 11 12 13 14 3A Fuse 15 4 16 17 18 19 20 21 22 23 24 25 Over Speed Relay Shut Down Relay Fuel Relay J1 J2 A J2 B J2 C J2 B B FUEL RELAY SHUTDOWN RELAY OVERSPEED RELAY CRANK SIGNAL RUN SIGNAL B B to aux starter solenoid Run signal switched B Battery Starter Auxiliary Starter Solenoid Fuel Pressure B Ground FR Energize to Stop solenoid FR Energize to Run solenoid Fuel relay N C dr...

Page 9: ...ing using the following formulas Refer to Table 4 4 1 to determine if the speed switch setting is below the factory setting listed If required frequency will be higher than the standard increase the setting before proceeding Turn the Overspeed Set pot clockwise to increase setting The adjustment is a 20 turn control without stops at either end 4 4 1 1 Be sure to have a fully charged battery to do ...

Page 10: ... not locked out may be tested as soon as the engine is running or may be tested without starting the engine by turning the Mode Selector switch to RUN position c To test other shutdowns a jumper wire can be used to short the input terminal for that circuit to ground terminal 4 Section 5 Operation 5 1 Operator Controls 5 1 1 Mode Selector Switch allows the operator to start the engine START run the...

Page 11: ...n engine run signal closes to ground at terminal 17 when the Mode Selector switch is in the RUN position and the engine is not shutdown by the MC 900 shutdown circuits 7 2 3 With the Mode Selector switch in the RUN position six of the eight shutdown TATTLETALE circuits are activated and will operate anytime a switch closes from ground to their inputs Circuit Input Output a Oil Pressure Terminal 28...

Page 12: ...5 7 5 0 0 29 0 0 7 5 7 5 7 5 7 5 7 5 7 5 30 0 0 7 5 7 5 7 5 7 5 7 5 7 5 31 0 0 7 5 7 5 7 5 7 5 7 5 7 5 32 0 0 7 5 7 5 7 5 7 5 7 5 7 5 33 0 0 7 5 7 5 7 5 7 5 7 5 7 5 34 0 0 0 0 0 0 0 0 35 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 36 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 37 2 13 8 27 6 13 8 27 6 13 8 27 6 0 0 38 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 39 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 40 13...

Page 13: ...Relay Qty Module 2 2 3 Model Number MC 900 2 24 Waukesha Part Number 40 35 0047 Control Display 40 00 0223 Relay Module 40 00 0224 Relay Part 00 00 2953 Relay Qty Module 2 Table 8 1 Table 8 2 CONTROL SYSTEMS SERVICES DIVISION P O Box 1819 Rosenberg Texas 77471 USA 1 281 633 4500 fax 1 281 633 4588 e mail sales fwmurphy com MURPHY DE MEXICO S A DE C V Blvd Antonio Rocha Cordero 300 Fracción del Agu...

Reviews: