© Munters AB, 2018
40
9
Calibration menu
•
•
•
•
9.1
Temperature
TEMP. CALIB. #01
Temp-1(Factor)► 0.0
Temp-2(Factor) 0.0
Temp-3(Factor) 0.0
Temp-4(Factor) n/a
The temperature sensor is a very accurate sensor with a deviation of 0.1. If needed, calibrate the
temperature sensor by using a very accurate reference instrument and enter the offset number for each
sensor in the Temp factor line. Use the up and down arrow keys to select sensors.
9.2
Humidity
If needed, calibrate the humidity sensor by using a very accurate reference instrument and enter the offset
number in the Humidity factor line.
9.3
Pressure
PRESS. CALIB. #01
Value A/D
Press ENTER to calib
9.4
Water & Feed
Water/Feed #01
Water per pulse 0.1
Feed per pulse 1.0
The water and feed system operates on a pulse counting method. Enter the amount of feed/water per
pulse.
HUM. CALIB. #01
Humid.(factor)► 0.0