If the inside temperature is above 21° C (heat temperature) the controller will operate according to the
Min Warm levels.
If the inside temperature is below 19° C (Soft Temp) the controller works according to Min Cold levels.
When the temperature is between 21°C and 19° C the controller creates a curve between the Min Cold
and Min Warm levels. For example, in 20° C the controller operates in level 5.
Important:
•
When using Soft Min according to inside temperature there is a curve between min warm and
min cold, while decreasing levels. When temperature increases the level remains at the lowest
level reached, until reaching the heat temperature.
•
When using Soft Min according to outside temperature there is a curve between min warm and
min cold while decreasing and increasing levels.
•
To select the type of minimum/maximum go to system parameters and change the level control
(see page 21).
5.3
Humidity
HUMIDITY #01
Target
Delay (minute)
Duration (sec)
0
0
0
Band (%)
Below Heat
2
NO
•
Target: Set the humidity target for.
•
Delay: Delay time before humidity treatment. The controller checks during the delay time whether
the humidity is above the target.
•
Duration: Humidity treatment duration time.
•
Band: Band zone to balance the treatment.
•
Below heat: Select if you wish to initiate humidity treatment below heater temperature.