5
Control menu
•
Temp Curve, page 19
•
Min. Max. Level, page 19
•
•
Static Pressure, page 22
•
System Parameters, page 24
•
Control Mode, page 25
5.1
Temp Curve
TEMP CURVE #01
#
Day
Target
Heat
Tunnel
Low Alarm
High Alarm
1
1
23.3
21.1
37.2
21.1
37.2
2
14
22.2
20.0
37.2
10.0
35.0
3
42
21.1
18.8
32.2
10.0
35.0
4
70
20.5
17.8
29.4
10.0
35.0
5
98
20.0
16.6
26.6
10.0
32.2
..10
The Pig Guard provides separate temperature curves for growth day, target temperature, heat
temperature, tunnel temperature and low/high alarm temperatures. The controller creates a curve for
each one and uses it as reference. The program will alter at midnight prior to the next day on the next
row programmed. There are up to 10 programmable rows, but the controller will maintain yesterday’s
settings for every empty line, therefore it is not necessary to fill the entire table.
Limits:
•
Day 0 - 999
•
Target 0 – 40
°
C
•
Alarm low 0 – 40
°
C (without floating point)
•
Alarm high 0 – 40
°
C (without floating point)
5.2
Min. Max. Level
By Day
Day Min Max
1 1 21
14 3 30
98 9 30
1