IceDry 30
5 - 10 m
Figure 4.4 Process air duct far away from door / air lock.
CA
CA
CAUTION!
UTION!
UTION!
Activate the main switch for the dehumidifier as soon as the unit has been installed. This allows the built-in heater
to operate and prevents internal ice formation.
The openings of inlet and outlet ducts must be well sealed during installation and operation stops, when the
dehumidifier is normally switched off. This prevents ice formation in ducts and dehumidifier caused by
unintended ventilation and low temperature in the cold-storage room.
4.7 Electrical connections
W
W
WARNING!
ARNING!
ARNING!
All electrical installations must be carried out by a qualified electrician and in accordance with local regulations.
All units are delivered complete with all internal cabling installed and configured to the voltage and
frequency given on the ID plate.
NOTE!
Supply voltage must not vary more than 10% of the specified operating voltage.
The unit must be adequately connected to earth.
For connection details, refer to the
ID plate
, Electrical circuit diagrams or section
. The
connection cable and main fuses must be suitable to the unit being installed.
Connect the unit with a flexible cable to a wall mounted socket. This way the unit can easily be disconnected
from the power supply by removing the plug from the socket.
The dehumidifier is connected to the external electrical cabinet via the supplied cables (about 10 m) with
marked connectors. A special bracket is provided for wall mounting of the external electrical cabinet.
190TEN-1049-H1307
Installation
12