9.2 Technical data
Process air
Rated airflow (m
3
/s)
0,833
Rated airflow (m
3
/h)
3000
Minimum available static pressure (Pa)
300
Fan motor power (kW)
3,0
Reactivation air
Rated airflow (m
3
/s)
0,175
Rated airflow (m
3
/h)
630
Minimum available static pressure (Pa)
300
Fan motor power (kW)
1,55
Rated Current
Current (Amps/Phase) 3~ 50 Hz 200 V
79,2
Current (Amps/Phase) 3~ 60 Hz 200V
79,2
Current (Amps/Phase) 3~ 50 Hz 230 V
65,2
Current (Amps/Phase) 3~ 50 Hz 380 V
39,4
Current (Amps/Phase) 3~ 50 Hz 400 V
38,0
Current (Amps/Phase) 3~ 50 Hz 415 V
36,8
Current (Amps/Phase) 3~ 60 Hz 440 V
36,2
Current (Amps/Phase) 3~ 60 Hz 460 V
35,1
Current (Amps/Phase) 3~ 60 Hz 480 V
33,8
Reactivation Heater
Temperature increase across heater (°C)
95
Reactivation Heater Power (kW)
18
Other Technical Data
Operating range for dehumidifier, ambient temperature (°C)
–25 to 0
Operating range for external electrical cabinet, ambient temperature (°C)
– for mounting in cool area
–25 to +10
– for mounting in warm area
+10 to +25
Drive motor power (W)
10
Reactivation fan heater power (W)
85
Output, heater in electrical cabinet (W)
150
Air filtration (standard)
G3
Electrical protection standard, dust and water resistant (main casing)
IP33
Fan Motor Winding Insulation Class
Klass F
Drive Motor Winding Insulation Class
Klass F
High Temperature Cut-Out (°C)
160 +/- 5
Contactor coil, voltage (V AC)
230
Table 9.2 Technical data