© Munters AB, 2013
18
5.3 Connection to the electrical system
The fan is supplied without a command and control circuit, but with all the internal electrical connections already
made.
At the fitting stage, the installer must set up a control panel in compliance with the requirements of standard IEC
EN 60439-1, and arrange the wiring of the fan in accordance with the instructions in standards IEC EN 60204-1
and IEC 60364.
The electrical panel of the fan must generally be equipped with the following devices (bearing EC marking as per
directive 2006/95/EC):
Lockable isolating switch.
Magnetothermic switch (chosen to suit the power of the motor).
The need to fit a switch of differential type depends on the configuration of the
electrical system supplying the fan: it is the installer’s responsibility to make this
assessment in accordance with the instructions in standard IEC 60364.
Red emergency stop button, mushroom type, provided with mechanical locking
and release by turning (in compliance with UNI EN ISO 13850). Operating the
button must bring about the electromechanical isolation of the power supply to the
electric motor (category 0/1 according to IEC EN 60204-1).
Start/stop selector switch (with characteristics compatible with the nominal current
of the motor), or main panel for managing the equipment, with control devices
which act on the electrical supply to the fan.
Do not supply power to the fan during installation stage.
Installer must issue a declaration of correct installation in accordance with
applicable legislation in the country of use.
WArNINg
Installation
Chapter5