© Munters AB, 2013
17
A-1997
fig. 4
B-1197
5.2 Installing Series EM fans
fig. 5
If the fan is fixed directly to a metal structure, M8
bolts type 8.8 must be used, screwing them into the
threaded inserts provided for the purpose on the
bodywork (two per side).
fig. 6
If the fan is installed in a masonry structure, an iron
outer frame must be constructed (not supplied with the
fan), with a 60 mm L-shaped profile at least 5 mm
thick, with suitably-sized clamps.
When the outer frame is properly built-in, i.e. perfectly
level and upright, insert the fan, screwing four M8 bolts
type 8.8 (not supplied with the fan) into the threaded
inserts provided on the sides of the bodywork, two per
side.
The fans must be installed to carry out extraction of the air present in the area,
and must not operate under positive pressure. It is also permissible to install the
fan in a horizontal position.
Installation
Chapter5
WArNINg