2. Define the following parameters:
o
Device: Read only column. Displays the device number.
o
the actual temperature drops differs from the
by this amount, heaters turn on. Range: -20 to +20. Default: 0.
o
the actual temperature differs from the
by this
amount, heaters turn off. Range: -20 to +20. Default: 0.556C° (-1F°).
o
the actual temperature differs from the
by this amount, heaters operate at their maximum output. Range: -20.0 to 20.0.
Default: -2.78C° (-5F°)
o
Min Output %: Define the minimum heater output. Range: 1 – 100%. Default: 0
o
Max Output %: Define the maximum heater output. Range: 1 – 100%. Default: 0
After defining the Minimum and Maximum Output Percentages, these
numbers become the goalposts for analog control. For example, if the
Maximum Output is defined as 80%, that number becomes the maximum
amount when calculating the curve.
NOTE
On Temp Diff and Off Temp Diff is calculated by average or some sensors of temperature
depends on definition in Temperature Definition Tables for each device.
3. If required, go to Control > Heaters > Set.