7. Go to System > Levels of Ventilation > Inlet & Curtain Levels and define the minimum opening
per levels. The controller will increase the opening according to the static pressure.
12.2.3
T
EMPERATURE
C
ONTROL
When set to temperature control, the air temperature controls the inlets' opening and closing. Inlets and
curtains open or close based on the difference between the current temperature and the target
temperature. Static pressure has no effect on opening or closing.
1. Go to System > Levels of Ventilation > Inlet & Curtain Levels > Set.
2. Define the following parameters:
o
Inlet Control by: Select Temperature.
o
Compensation By Degree: This parameter defines how much the inlets open or close
based on the difference between the target temperature and current temperature. If,
for example, there is a 2° difference and the compensation is 5%, the inlets open by
10%.
o
Delay for Compensation (min): The divergence in temperatures must continue for this
amount of time before any change is made in the inlet openings.
o
Max Compensation Opening: This parameter defines the maximum possible opening.
Even if the calculated compensation is greater than this amount, the inlets will not open
more than this amount.