4. Define the following parameters:
o
Temperature Band: The temperature defines the temperature range above the target
for which the current level of ventilation is satisfactory. The temperature band takes
effect only if there is no diff defined for these levels and only after the increase delay
time. Ventilation level increases until the temperature returns to the target temperature
or a level's diff is defined. Range: 0.2 – 5.0° C
o
Cool Down Factor (%): If
the temperature increases enough to push Element to go to the next level
but then the average temperature decreases by this percentage within the
Level Increase Delay, Element delays the level increase. In effect, this function
resets the Level Increase Delay.
o
Quick Decrease Level Temp: If the temperature decreases by this factor, Element
decreases the ventilation level even if the Level Decrease Delay Time has not passed.
Range: 0 – 20%
o
Level Increase Delay (sec): Define the amount of time that Elements delays increasing
the ventilation level.
o
Level Decrease Delay (sec): Define the amount of time that Elements delays decreasing
the ventilation level.
o
V.Fan Cycle Output Mode: Element enables limiting the variable fans' output range.
Low Mode:
o
Off: Off.
On: Percentage per level
High Mode:
o
Off: Percentage per level.
o
On: 100%
o
Stir Fan Operate During Cycle: While in Cycle mode Element enables the stir fan to
work with the fans in a synchronous or asynchronous manner.
On: Stir fans operate during the On cycle time.
Off: Stir fans operate during the Off cycle time.