Table 6.2: Wall mounted heating capacity (continued)
Capacity
(kW)
Outdoor air
temperature (°C)
Indoor air temperature (°C DB)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
WB
DB
kW
kW
kW
kW
kW
kW
5.6
-20
-19.8
3.53 3.53 3.53 3.53 3.53 3.53
-19
-18.8
3.78 3.78 3.78 3.78 3.78 3.78
-17
-16.7
3.97 3.97 3.97 3.97 3.97 3.97
-15
-14.7
4.10 4.10 4.10 4.10 4.10 4.10
-13.00
-12.60
4.22 4.22 4.22 4.22 4.22 4.22
-11.00
-10.50
4.41 4.41 4.41 4.41 4.41 4.41
-10.00
-9.50
4.60 4.60 4.60 4.60 4.60 4.60
-9.10
-8.50
4.73 4.73 4.73 4.73 4.73 4.73
-7.60
-7.00
4.79 4.79 4.79 4.79 4.79 4.79
-5.60
-5.00
4.98 4.98 4.98 4.98 4.98 4.98
-3.70
-3.00
5.23 5.23 5.23 5.23 5.23 5.23
-0.70
0.00
5.61 5.61 5.61 5.61 5.61 5.29
2.20
3.00
5.92 5.92 5.92 5.92 5.80 5.29
4.10
5.00
6.11 6.11 6.11 6.11 5.80 5.29
6.00 7.00 6.30
6.30
6.30
6.11 5.80 5.29
7.90
9.00
6.49 6.49 6.30 6.11 5.80 5.29
9.80
11.00
6.68 6.68 6.30 6.11 5.80 5.29
11.80
13.00
6.93 6.80 6.30 6.11 5.80 5.29
13.70
15.00
7.12 6.80 6.30 6.11 5.80 5.29
7.1
-20
-19.8
4.48 4.48 4.48 4.48 4.48 4.48
-19
-18.8
4.80 4.80 4.80 4.80 4.80 4.80
-17
-16.7
5.04 5.04 5.04 5.04 5.04 5.04
-15
-14.7
5.20 5.20 5.20 5.20 5.20 5.20
-13.00
-12.60
5.36 5.36 5.36 5.36 5.36 5.36
-11.00
-10.50
5.60 5.60 5.60 5.60 5.60 5.60
-10.00
-9.50
5.84 5.84 5.84 5.84 5.84 5.84
-9.10
-8.50
6.00 6.00 6.00 6.00 6.00 6.00
-7.60
-7.00
6.08 6.08 6.08 6.08 6.08 6.08
-5.60
-5.00
6.32 6.32 6.32 6.32 6.32 6.32
-3.70
-3.00
6.64 6.64 6.64 6.64 6.64 6.64
-0.70
0.00
7.12 7.12 7.12 7.12 7.12 6.72
2.20
3.00
7.52 7.52 7.52 7.52 7.36 6.72
4.10
5.00
7.76 7.76 7.76 7.76 7.36 6.72
6.00 7.00 8.00
8.00
8.00
7.76 7.36 6.72
7.90
9.00
8.24 8.24 8.00 7.76 7.36 6.72
9.80
11.00
8.48 8.48 8.00 7.76 7.36 6.72
11.80
13.00
8.80 8.64 8.00 7.76 7.36 6.72
13.70
15.00
9.04 8.64 8.00 7.76 7.36 6.72
Abbreviations:
TC: Total capacity
Notes:
1.
Shaded cells indicate rating condition.
Table continued on next page …
The 2
nd
Generation DC Series VRF Indoor Units