The 2
nd
Generation DC Series VRF Indoor Units
18
201806
Table 6.2: Wall mounted heating capacity
(continued)
Capacity
(kW)
Outdoor air
temperature (°C)
Indoor air temperature (°C DB)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
WB
DB
kW
kW
kW
kW
kW
kW
3.6
-20
-19.8
2.24 2.24 2.24 2.24 2.24 2.24
-19
-18.8
2.40 2.40 2.40 2.40 2.40 2.40
-17
-16.7
2.52 2.52 2.52 2.52 2.52 2.52
-15
-14.7
2.60 2.60 2.60 2.60 2.60 2.60
-13.00
-12.60
2.68 2.68 2.68 2.68 2.68 2.68
-11.00
-10.50
2.80 2.80 2.80 2.80 2.80 2.80
-10.00
-9.50
2.92 2.92 2.92 2.92 2.92 2.92
-9.10
-8.50
3.00 3.00 3.00 3.00 3.00 3.00
-7.60
-7.00
3.04 3.04 3.04 3.04 3.04 3.04
-5.60
-5.00
3.16 3.16 3.16 3.16 3.16 3.16
-3.70
-3.00
3.32 3.32 3.32 3.32 3.32 3.32
-0.70
0.00
3.56 3.56 3.56 3.56 3.56 3.36
2.20
3.00
3.76 3.76 3.76 3.76 3.68 3.36
4.10
5.00
3.88 3.88 3.88 3.88 3.68 3.36
6.00 7.00 4.00
4.00
4.00
3.88 3.68 3.36
7.90
9.00
4.12 4.12 4.00 3.88 3.68 3.36
9.80
11.00
4.24 4.24 4.00 3.88 3.68 3.36
11.80
13.00
4.40 4.32 4.00 3.88 3.68 3.36
13.70
15.00
4.52 4.32 4.00 3.88 3.68 3.36
4.5
-20
-19.8
2.80 2.80 2.80 2.80 2.80 2.80
-19
-18.8
3.00 3.00 3.00 3.00 3.00 3.00
-17
-16.7
3.15 3.15 3.15 3.15 3.15 3.15
-15
-14.7
3.25 3.25 3.25 3.25 3.25 3.25
-13.00
-12.60
3.35 3.35 3.35 3.35 3.35 3.35
-11.00
-10.50
3.50 3.50 3.50 3.50 3.50 3.50
-10.00
-9.50
3.65 3.65 3.65 3.65 3.65 3.65
-9.10
-8.50
3.75 3.75 3.75 3.75 3.75 3.75
-7.60
-7.00
3.80 3.80 3.80 3.80 3.80 3.80
-5.60
-5.00
3.95 3.95 3.95 3.95 3.95 3.95
-3.70
-3.00
4.15 4.15 4.15 4.15 4.15 4.15
-0.70
0.00
4.45 4.45 4.45 4.45 4.45 4.20
2.20
3.00
4.70 4.70 4.70 4.70 4.60 4.20
4.10
5.00
4.85 4.85 4.85 4.85 4.60 4.20
6.00 7.00 5.00
5.00
5.00
4.85 4.60 4.20
7.90
9.00
5.15 5.15 5.00 4.85 4.60 4.20
9.80
11.00
5.30 5.30 5.00 4.85 4.60 4.20
11.80
13.00
5.50 5.40 5.00 4.85 4.60 4.20
13.70
15.00
5.65 5.40 5.00 4.85 4.60 4.20
Abbreviations:
TC: Total capacity
Notes:
1.
Shaded cells indicate rating condition.
Table continued on next page …