background image

 

MTRA-FSP Installation & Operation Manual 

 

 
 

 
00242600-MTRA-FSP_Manual.doc 

Page 13 of 16 

 

6.2.2 

Thermal Backup (BU) Input 

The MTRA-FSP can be used as a backup pump control device for the 
MultiSmart Pump Controller and RTU. When used as a backup, the Thermal 
sensor is wired into the Thermal input, and the MultiSmart Thermal input is 
wired into the MTRA-FSP Thermal BU input. 

6.2.3 

Failsafe Probe Alarm Input 

MultiTrode probes can be sold with an extra connection to the top sensor for 
failsafe detection.  This is used to detect if the probe sensor cable has broken 
by checking there is a circuit. If the cable is broken, there will be no circuit back 
to the failsafe input and an alarm will be raised. 

When a failsafe alarm occurs the Probe LED flashes and the Failsafe Alarm 
output contacts are activated.  Also the pump contacts will be deactivated so 
the pump cannot run until the fault condition is removed. 

 

 

NOTE:

 

If a non-failsafe probe is used then a jumper must be connected 
between the Alarm Probe and Failsafe Inputs to prevent Probe 
Fault Alarms occurring.

 

 

NOTE: 

The failsafe probe input must be connected to the highest probe in 
the system if used. 

 

6.2.4 

Assumed Probe Faults 

If a High Level, or High Alarm input is activated and the Low Level probe is 
deactivated, then the relay assumes the Low Level probe is faulty.  

This condition is called an “Assumed Probe Fault”. The relay indicates this 
condition by flashing the Level Alarm LED - single pulse on, 3s off. 

The relay will also change its pumping behaviour to a timed method until the 
fault condition is no longer present. See the assumed probe fault notes in 
Sections 5.1 and 5.2. 

 

Summary of Contents for MTRA-FSP

Page 1: ...MTRA FSP Level Control Relay Installation Operation Manual...

Page 2: ...Ltd in Australia USA and many countries worldwide PUMPVIEW is a registered trademark of MultiTrode Pty Ltd in Australia Design registration is pending for the MultiSmart Pump Controller Remote and Ba...

Page 3: ...troduction 5 3 Specifications 5 4 Installation 6 4 1 Power Supply 6 4 2 DIP Switch Settings 7 5 Operation Modes 8 5 1 Empty Discharge Mode 8 5 2 Fill Charge Mode 10 6 Alarms 12 6 1 Level Alarms AL Pro...

Page 4: ...ds DANGER This symbol is used where non compliance could result in injury or death WARNING This symbol is used where non compliance could result in incorrect operation damage to or failure of the equi...

Page 5: ...rent status including Pump On Off Thermal Fault Probe Fault and Level Alarm The MTRA FSP level control relay is designed to be easy to install and configure All connections are clearly labelled on the...

Page 6: ...nd an overcurrent protection device must be included in the installation The disconnection device must be in close proximity to the equipment and within easy reach of the operator and be marked as the...

Page 7: ...de 5 1 1 ON Fill Charge Mode 5 2 OFF High Level Alarm 6 1 2 ON Low Level Alarm 6 1 OFF 0 5 sec Pump Activation and Deactivation Delay 8 2 3 ON 10 sec Pump Activation and Deactivation Delay 8 2 OFF Con...

Page 8: ...ay and also the Pump Relay in case the high level probe has failed The pump will continue to operate until the liquid level drops below the low level probe and the pump deactivation period expires A t...

Page 9: ...MTRA FSP Installation Operation Manual 00242600 MTRA FSP_Manual doc Page 9 of 16...

Page 10: ...The pump will continue to operate until the liquid level rises to the high level probe and the pump deactivation period expires A thermal fault will deactivate the pump regardless of liquid level A Pr...

Page 11: ...MTRA FSP Installation Operation Manual 00242600 MTRA FSP_Manual doc Page 11 of 16...

Page 12: ...he Alarm contacts can be used to operate an alarm device such as a light or siren The alarm output can be set to Normally Open NO or Normally Closed NC using DIP Switch 6 NC alarm output DIP Switch OF...

Page 13: ...occurs the Probe LED flashes and the Failsafe Alarm output contacts are activated Also the pump contacts will be deactivated so the pump cannot run until the fault condition is removed NOTE If a non f...

Page 14: ...buttons wired into the Manual Hand input and the Off input 7 1 Manual Operation of Pump Hand Manual pump operation works as follows Pushing the Manual Hand button will start the pump The pump will con...

Page 15: ...vity can be changed using dip switches 7 and 8 if the sensitivity needs adjustment to allow for different types of liquid DIP Switch 7 8 Sensitivity OFF OFF 1 kohm ON OFF 4 kohm OFF ON 20 kohm ON ON 8...

Page 16: ...Steady Thermal Thermal fault active Flashing Assumed probe fault Steady Probe Failsafe alarm active Flashing MultiTrode Pty Ltd Head Office Brisbane Technology Park 18 Brandl Street PO Box 4633 Eight...

Reviews: