background image

 

  MTRA-FSP Installation & Operation Manual 

 

 
 

 
Page 12 of 16 

00242600-MTRA-FSP_Manual.doc 

Alarms 

The MTRA-FSP has the following alarm inputs: 

6.1  Level Alarms (AL Probe) 

A conductive level sensor is connected to the AL Probe input to detect when the 
liquid level has risen above or below an acceptable level. 

 

In  Empty  (Discharge)  mode  this  will  be  a  high  level  alarm  and  will 

activate  when  the  AL  Probe  input  detects  liquid  and  the  activation 
delay has expired. 

 

In  Fill  (Charge)  mode  this  will  be  a  low  level  alarm  and  will  activate 

when the AL Probe input is no longer detecting level (ie: the level has 
dropped below the sensor) and the activation delay has expired. 

When a level alarm is detected the Alarm contacts are activated and the Level 
Alarm LED flashes. The Alarm contacts can be used to operate an alarm device 
such as a light or siren. 

The alarm output can be set to Normally Open (NO) or Normally Closed (NC) 
using DIP Switch 6: 

 

NC alarm output (DIP Switch OFF) 

 

NO alarm output (DIP Switch ON) 

The alarm output can be configured to toggle (to flash an alarm light for 
example). This is set using DIP Switch 4: 

 

Constant alarm output (DIP Switch OFF) 

 

Flashing alarm output (DIP Switch ON) 

6.2  Pump Alarms 

There are two types of pump alarms supported by the MTRA-FSP – Thermal 
and Seal. 

6.2.1 

Thermal Alarm Input 

A pump thermal sensor can be wired into the Thermal input. This is used to 
detect when the pump is overheating due to a blockage or other fault. 

When a thermal alarm is detected the Thermal output contacts are activated 
and the Thermal Fault LED flashes. The thermal alarm will also turn off the 
pump if it is running. The pump will not be able to be switched on again until the 
thermal alarm condition is cleared.

Summary of Contents for MTRA-FSP

Page 1: ...MTRA FSP Level Control Relay Installation Operation Manual...

Page 2: ...Ltd in Australia USA and many countries worldwide PUMPVIEW is a registered trademark of MultiTrode Pty Ltd in Australia Design registration is pending for the MultiSmart Pump Controller Remote and Ba...

Page 3: ...troduction 5 3 Specifications 5 4 Installation 6 4 1 Power Supply 6 4 2 DIP Switch Settings 7 5 Operation Modes 8 5 1 Empty Discharge Mode 8 5 2 Fill Charge Mode 10 6 Alarms 12 6 1 Level Alarms AL Pro...

Page 4: ...ds DANGER This symbol is used where non compliance could result in injury or death WARNING This symbol is used where non compliance could result in incorrect operation damage to or failure of the equi...

Page 5: ...rent status including Pump On Off Thermal Fault Probe Fault and Level Alarm The MTRA FSP level control relay is designed to be easy to install and configure All connections are clearly labelled on the...

Page 6: ...nd an overcurrent protection device must be included in the installation The disconnection device must be in close proximity to the equipment and within easy reach of the operator and be marked as the...

Page 7: ...de 5 1 1 ON Fill Charge Mode 5 2 OFF High Level Alarm 6 1 2 ON Low Level Alarm 6 1 OFF 0 5 sec Pump Activation and Deactivation Delay 8 2 3 ON 10 sec Pump Activation and Deactivation Delay 8 2 OFF Con...

Page 8: ...ay and also the Pump Relay in case the high level probe has failed The pump will continue to operate until the liquid level drops below the low level probe and the pump deactivation period expires A t...

Page 9: ...MTRA FSP Installation Operation Manual 00242600 MTRA FSP_Manual doc Page 9 of 16...

Page 10: ...The pump will continue to operate until the liquid level rises to the high level probe and the pump deactivation period expires A thermal fault will deactivate the pump regardless of liquid level A Pr...

Page 11: ...MTRA FSP Installation Operation Manual 00242600 MTRA FSP_Manual doc Page 11 of 16...

Page 12: ...he Alarm contacts can be used to operate an alarm device such as a light or siren The alarm output can be set to Normally Open NO or Normally Closed NC using DIP Switch 6 NC alarm output DIP Switch OF...

Page 13: ...occurs the Probe LED flashes and the Failsafe Alarm output contacts are activated Also the pump contacts will be deactivated so the pump cannot run until the fault condition is removed NOTE If a non f...

Page 14: ...buttons wired into the Manual Hand input and the Off input 7 1 Manual Operation of Pump Hand Manual pump operation works as follows Pushing the Manual Hand button will start the pump The pump will con...

Page 15: ...vity can be changed using dip switches 7 and 8 if the sensitivity needs adjustment to allow for different types of liquid DIP Switch 7 8 Sensitivity OFF OFF 1 kohm ON OFF 4 kohm OFF ON 20 kohm ON ON 8...

Page 16: ...Steady Thermal Thermal fault active Flashing Assumed probe fault Steady Probe Failsafe alarm active Flashing MultiTrode Pty Ltd Head Office Brisbane Technology Park 18 Brandl Street PO Box 4633 Eight...

Reviews: