20
VersaTemp™ Water-to-Water Heat Pumps
ARA-CAT-001 0816
New
FWB
1065 Maple Avenue P.O. Box 510 Sparta, WI 54656
Phone 608-366-2400 • [email protected]
www.multistack.com
Originators…
Multistack invented the modular water chiller. It started with a radically simple idea: chiller modules that could be brought into the
equipment room one at a time, through standard doorways and down elevators, to form a fully integrated chiller system. The idea
launched a revolution and transformed Multistack into a leader in the commercial water-chiller industry.
Innovators…
Multistack perfected the modular chiller and leads the industry in innovative and environmentally friendly modular solutions.
Since founding in the late 1980s, Multistack has engineered, manufactured, and distributed an impressive array of modular air
conditioning firsts: the first on-board strainer, the first modular automatic blow-down device, the first modular chiller for variable
flow, the first modular chiller-heater (heat pump), the first modular heat-recovery chiller, the first modular air-to-water heat pump,
the first modular chiller to utilize MagLev™ compressor technology, and the first modular chiller to utilize R-410A.
Never the Imitators…
Multistack sets the standard in the industry for superior customer service, fast and on time shipment, superior product quality, and
new product development. Our pioneering leadership in environmental issues is well documented. If you want the best, be sure to
specify the original – Multistack®.
3.02 Water Treatment Requirements
A. Supply water for the chilled water circuit shall be analyzed and treated by a professional water treatment specialist who is familiar with the
operating conditions and materials of construction specified for the chiller’s heat exchangers, headers and associated piping. Cycles of
concentration shall be controlled such that recirculated water quality for modular chillers using 316 stainless steel brazed plate heat exchangers
and carbon steel headers is maintained within these parameters:
1. pH
Greater than 7 and less than 9
2. Total Dissolved Solids (TDS)
Less than 1000 ppm
3. Hardness as CaCO
3
30 to 500 ppm
4. Alkalinity as Ca CO
3
30 to 500 ppm
5. Chlorides
Less than 200 ppm
6. Sulfates
Less than 200 ppm
3.03 Warranty and Start-Up
A. Manufacturer’s Warranty: Manufacturer shall provide full parts-only warranty coverage for entire chiller for a period of one year. All parts shall be
warranted against defects in material and workmanship. Similar parts-only coverage shall be provided for the chillers compressors for a period
of five years. The warranty period shall commence either on the equipment start-up date or six months after shipment, whichever is earlier.
B. Manufacturer shall provide the services of a factory authorized service engineer to provide complete start-up supervision. The factory authorized
service engineer shall also be responsible for assembly of the chillers cabinetry package and electrical bus bar system. After start-up a
manufaturer’s representative shall provide a minimum of eight hours of operator training to the owner’s designated representative(s).
Guide Specifications
Multistack has a policy of continual improvement and reserves the right to change product design, literature and specifica-
tions without notice. For more information on this and other Multistack products, contact your nearest Multistack dealer.