background image

19

VersaTemp™ Water-to-Water Heat Pumps

Guide Specifications

 7.  OPTIONAL: Interoperability

          The chiller shall be capable of interfacing to a building automation system.  Interface shall be accomplished using an Interoperability Web portal 

          and shall be capable of communication over BACNet, Modbus or LON.

I.  Chiller shall have external inputs and outputs to be compatible with the building management system to include remote start/stop capability 

     and cooling alarm output.

J. Each refrigerant circuit shall include all refrigerant specialties including a properly sized dynamic receiver to provide reliable operation down to 

     40 F ambient. 

K. OPTIONAL:  Single Point Power Connection 

     Chiller shall be provided with a single point power connection at a 5,000 amp SCCR.  This will include pre-engineered wiring for field 

      installation and connection to a factory mounted chiller junction box.  Junction box shall include branch circuit protection for each module 

      and provide a single connection point to building power.

a. OPTIONAL—SCCR greater than 5,000 amps:  Contact factory.  Depending on voltage and module size SCCR up to 85,000 may be available. 

    Some higher SCCR will require fused protection as opposed to the standard isolation circuit breakers.

L. 

OPTIONAL:

 Variable Flow Operation – Chilled Water

Butterfly type isolation valves shall incorporate appropriate accessories and controls to allow the chiller to operate efficiently in a variable primary flow 

system.  Motorized valve per module shall operate for variable flow.

M.  

OPTIONAL:

  Pump Module

  Provide a pump module of size and capacity indicated on the drawings and schedules.  The pump module shall be interconnected though the common   

  chiller header system and require no additional water connections.  Pump module will become an integral part of the chiller system.  The pump module 

  shall incorporate dual in-line centrifugal pumps in a primary/standby pumping arrangement.  Pump starters and controls shall be provided to enable 

  manual selection of lead pump.  In addition, in the event of a loss-of-flow failure of the chilled water system, the pump module controls shall disable the 

  lead pump and automatically start the standby pump.  The module shall be completely factory assembled and tested prior to shipment.

N.  

OPTIONAL: 

Lifting Frame

 Optional six-inch I-beam painted steel frame will be provided with all modules mounted upon it.  Typically, all water and wiring connections will be made  

  between the modules at the factory.  Depending on chiller length or customer requests, larger I-beams can be furnished.  

2.03 SAFETIES, CONTROLS AND OPERATION

A. The chiller safety controls shall be provided (minimum) as follows:

1.  Low evaporator refrigerant pressure

2.  Loss of water flow through the evaporator

3.  High condenser refrigerant pressure

4.  High compressor motor temperature

5.  Low suction gas temperature

6.  Low leaving evaporator water temperature

B. Failure of chiller to start or chiller shutdown due to any of the above safety cutouts shall be annunciated by display of the appropriate diagnostic 

     description at the unit control panel.  This annunciation will be in plain English.  Alphanumeric codes shall be unacceptable.

C.  The chiller shall be furnished with a master controller as an integral portion of the chiller control circuitry to provide the following functions:

1.  Provide automatic chiller shutdown during periods when the load level decreases below the normal operating requirements of the chiller.  Upon 

      an increase in load, the chiller shall automatically restart.

2.   Provisions for connection to automatically enable the chiller from a remote energy management system.

3.  The control panel shall provide alphanumeric display showing all system parameters in the English language with numeric data in English units.

D.  Normal Chiller Operation

1.  When chiller is enabled, the factory supplied master controller modulates the chiller capacity from minimum to maximum as required by 

     building load.

2.  The chiller control system shall respond to entering water temperature and will have an integral reset based on entering water temperature to 

      provide for efficient operation at part-load conditions.

PART 3  INSTALLATION

3.01 PIPING SYSTEM FLUSHING PROCEDURE

A. Prior to connecting the chiller to the building chilled water loop, the piping shall be flushed with a detergent and hot water (110-130° F) mixture 

     to remove previously accumulated dirt and other organic residue.  In old piping systems with heavy encrustation of inorganic materials consult a 

     water treatment specialist for proper passivation and/or removal of these contaminants. 

B. During the flushing a 30 mesh (max.) Y-strainers (or acceptable equivalent) shall be in place in the system piping and examined periodically as 

     necessary to remove collected residue. The use of on board chiller strainers shall not be acceptable. The flushing process shall take no less than six 

      hours or until the strainers, when examined after each flushing, are clean.  Old systems with heavy encrustation shall be flushed for a minimum of 

     24 hours and may take as long as 48 hours before the filters run clean.  Detergent and acid concentrations shall be used in strict accordance with 

     the respective chemical manufacturers instructions.  After flushing with the detergent and/or dilute acid concentrations the system loop shall be 

     purged with clean water for at least one hour to ensure that all residual cleaning chemicals have been flushed out.  

C. Before supplying water to the chiller the Water Treatment Specification shall be consulted for requirements regarding the water quality during 

     chiller operation.  The appropriate chiller manufacturer’s service literature shall be available to the operator and/or service contractor and 

     consulted for guidelines concerning preventative maintenance and off-season shutdown procedures.

Continued on next page. 

Summary of Contents for AirStack VersaTemp ARA 020X

Page 1: ...1 VersaTemp Water to Water Heat Pumps 1 Air Cooled Template VersaTemp Water to Water Heat Pump with Auxiliary Air Cooled Coil Product Data Catalog ARA 020X 030X 060X Modules...

Page 2: ...er to Water Heat Pumps Contents ARA Features Benefits 3 Model Number Nomenclature 4 5 General Information 6 7 Unit Dimensions Configurations 8 15 Electrical Piping Requirements 16 Guide Specifications...

Page 3: ...ith refrigerant and are factory run tested prior to shipment on an AHRI certified test stand ARA modules are ETL listed according to UL Standard 1995 and CSA certified per Standard C22 2 236 Compresso...

Page 4: ...Heat Pump 4 A Brazed SS V Other 5 A Cu tube Al fin B Cu tube Cu fin V Other 6 A None B Bronzeglow H Heresite E Electrofin S Standard V Other 7 E ECM Fans H High static L Single Fan V Other 8 R 410A P...

Page 5: ...60 H 460 3 60 C 575 3 60 D 200 3 50 E 400 3 50 F 380 3 60 S 220 230 1 60 V Other Accessory Module ACP 2 H C 180 M B S C TankVolume Three digits 000 None Gallons Water Piping C Copper S Stainless P PVC...

Page 6: ...4 1 Quantity 2 2 4 FanType Axial Axial Axial Fan Material Composite Composite Composite Air Flow Per Module per module 16 000 22 000 44 000 Air Cooled Coil ARA 020X ARA 030X ARA 060X Fin Material Alu...

Page 7: ...sword levels provide three different access modes to the parameters read only for assistance edit for servicing and total access for the manufacturer Additional features include WiFi interface for tab...

Page 8: ...s Typical Unit Dimensions ARA 020X Single Module Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recom mend pit installations Consult Mul...

Page 9: ...ps Typical Unit Dimensions ARA 030X Single Module Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Page 10: ...umps Typical Unit Dimensions ARA 030X Two Modules Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Page 11: ...Dimensions Typical Unit Dimensions ARA 020X with ASP 020X Units CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recom mend pit installations Consult...

Page 12: ...mps Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Multistack Representative for options Typical Uni...

Page 13: ...umps Typical Unit Dimensions ARA 060X Two Modules Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Page 14: ...mps Typical Unit Dimensions ARA 060X Four Modules Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Page 15: ...ps Dimensions Typical Unit Dimensions ARA 060X Multiwing Fans CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mu...

Page 16: ...the other compressors in the system The total system Minimum Circuit Ampacity MCA shall not exceed 760A Wire sizing is based ontheNationalElectricCode NEC ratingfor75 Ccopperwire threewiresperconduit...

Page 17: ...structions for transporting rigging and assembly of modular chiller 1 06 WARRANTY A Manufacturer s equipment warranty shall be for a period of one 1 year from date of equipment start up or 18 months f...

Page 18: ...essure reductions at 30 feet as compared to standard fan option ranges from 3 6 dBA H Central Control System 1 Scheduling of the various compressors shall be performed by a microprocessor based contro...

Page 19: ...suction gas temperature 6 Low leaving evaporator water temperature B Failure of chiller to start or chiller shutdown due to any of the above safety cutouts shall be annunciated by display of the appr...

Page 20: ...a professional water treatment specialist who is familiar with the operating conditions and materials of construction specified for the chiller s heat exchangers headers and associated piping Cycles...

Reviews: