background image

U-20806/U-20807 Adjustable Vertical Indicator Posts

Installation

6

11. Using the Wrench, open and 

close the valve and check to see 

that the “SHUT” and “OPEN” Targets 

are clearly in view in the Windows, 

at their respective positions, and 

that there is no feeling of binding 

of the Upper or Lower Stem 

Assemblies. It is recommended 

that the turns to open/close be 

counted and compared to the valve 

manufacturer’s specification, in order 

to verify full valve opening.
NOTES: If there is any indication 

of binding of the internal operating 

parts, the vertical alignment of the 

Indicator Post must be corrected. If 

the Target Plates are not properly in 

view, completely close the PIV and 

then repeat Steps 6 – 11. 
12. Loosen the two Cap Screws at 

the base of the Upper Barrel and 

then slide the Post Head up until 

the Bury Line of the Post Head 

coincides with the planned finish 

grade. Tighten the two Set Screws 

at the base of the Post Head with 

a torque of 40 to 60 ft.lbs. When 

properly installed, the center line 

of the Target Windows will be 30” 

above the finish grade.
13. Back fill to final grade and repeat 

Step 11.
14. Tighten the switch mounting hole 

plug if the Supervisory Control Valve 

Switch is not to be immediately 

attached.
15. Install the Supervisory Control 

Valve Switch (supplied by customer)

 

a) Remove the Cover from the 

assembly, and then loosen the 

Trip Rod Locking Screw. Adjust 

the position of the Trip Rod so 

that it extends about 1

3

/

8

” beyond 

the Nipple, and then securely 

tighten the Trip Rod Locking 

Screw.

b) Rotate the Post Operating Nut 

until the PIV is fully open. Note 

the position of one of the “OPEN” 

Targets in its Window.

c) Rotate the Operating Stem until 

the “OPEN” Targets are out of the 

Post Windows. Note the direction 

in which the “OPEN” Target will 

move when it is returned to the 

Post Window.

d) Remove the Nipple from the 

assembly, and then with the 

Locknut screwed over the Nipple 

threads, hand tighten the Nipple 

into the 

1

/

2

” NPT hole provided in 

the Post Head, and then tighten 

the Locknut against the Post 

Head to secure the Nipple firmly 

in place. 

e) Refer to “Positioning of Targets” 

(pg. 5) as appropriate, and note 

the direction in which the Trip Rod 

must move when the “OPEN” 

Target is returned to the Post 

Window. Slide the assembly 

as far as possible onto the 

Nipple while maintaining proper 

orientation of the assembly, and 

then tighten the Set Screw that 

holds the assembly onto the 

Nipple.

f) Attach leads from an electrical 

continuity meter to the 

appropriate terminals.

g) Return the valve to its fully open 

position. Verify that the “OPEN” 

Target returns to the position 

noted in Step b. Also, verify that 

the Switch contacts change 

position within two turns of the 

valve being fully open.

h) Begin to return the valve to its 

closed position. Verify that the 

Switch contacts change back to 

their original position within two 

turns from full open.
NOTE: If the Upper Stem 

Assembly binds before the 

“OPEN” Target reaches its 

full open position, or the 

switch contacts do not change 

position as described in Steps 

g and h, then the Targets must 

be readjusted.
If the Targets require 

readjustment, close the PIV, 

remove the Switch assembly, 

and repeat Steps 6 and 11; 

however, when positioning the 

Targets, rotate both Targets at 

attachment of sUperVisory 

control ValVe switch

Left-Hand Opening Valves

targets

move 

Up as 

Valve is 

shut

Left-Hand 

Opening Valve is 

Shut by Turning 

Wrench to the 

Right (Clockwise)

switch

actuator

rod

pcVs-2

target 

switch 

trip rail

Right-Hand Opening Valves

targets

move down 

as Valve is 

shut

Right-Hand 

Opening Valve is 

Shut by Turning 

Wrench to the Left 

(Counterclockwise)

switch

actuator

rod

pcVs-2

target 

switch 

trip rail

the same time as necessary so 

that the “OPEN” target will trip 

the Actuator Rod of the Switch. 

Repositioning of the “OPEN” 

and “SHUT” Targets relative 

to each other should not be 

necessary. Repeat Steps b – h.

 i) Remove the electrical continuity 

test leads. The external field 

wiring connections can now be 

made to the Switch.
NOTE: Use of a weathertight 

conduit connector with a 

gasket seal is recommended.

Summary of Contents for U-20806

Page 1: ...r training and periodic review regarding the use of this equipment is essential to prevent possible serious injury and or property damage The instructions contained herein were developed for using thi...

Page 2: ...ound water supply to automatic sprinkler water spray deluge foam water deluge or standpipe fire protection systems They permit operation of underground valves while providing an above ground visual in...

Page 3: ...ed by each Order Length for the 4 24 USPVH Resilient Wedge PIVs based on the typical diameter of underground pipe For PIVs with different B dimensions the minimum and maximum trench depths which will...

Page 4: ...Min Max Min Max Min Max 16 4 10 6 8 6 5 8 5 8 2 10 2 9 11 11 11 11 8 13 8 13 5 15 5 18 5 5 7 3 7 0 9 0 8 9 10 9 10 6 12 6 12 3 14 3 14 0 16 0 20 5 10 7 8 7 4 9 5 9 1 11 2 10 10 12 11 12 7 14 8 14 4 16...

Page 5: ...ith the center of the Post Head Coupling clearances can accommodate a maximum pipe slope of 5 degrees It is recommended that a spirit level be used to set the vertical alignment of the Indicator Post...

Page 6: ...e into the 1 2 NPT hole provided in the Post Head and then tighten the Locknut against the Post Head to secure the Nipple firmly in place e Refer to Positioning of Targets pg 5 as appropriate and note...

Page 7: ...Short Cotter Pin 290158 17 Threaded Sleeve U 20806 148634 U 20807 241011 18 Upper Stem 148633 19 Weather Cap 290143 20 Retaining Ring 290157 21 OPEN Target U 20806 290144 U 20807 290552 22 SHUT Targe...

Page 8: ...Indicator Post should also be physically tried to be sure that the valve is in the fully open position if there are any damaged parts sign of tampering or the position of the valve is questionable NO...

Reviews: