7.21.2 Differential pressure gage – Alarm function check
WARNING
Fuels are combustible and explosive.
Risk of fire and explosion!
• Avoid open flames, electrical sparks and ignition sources.
• Do not smoke.
• Wear protective clothing, protective gloves, and safety glasses / facial protection.
Checking differential pressure gage alarm function
1.
Switch on fuel treatment system (→ Page 80).
2.
Set the alarm points at the differential pressure gage to zero.
Result:
Alarm is issued after preset time.
3.
Reset alarm points at differential pressure gage.
MS150046/03E 2018-08
| Fuel Supply System | 213
TIM-ID: 0000007737 - 007