208 – SD P-Charge Air
Yellow alarm; power limitation < 20%;
Cause
Corrective action
Charge-air pressure sensor
faulty; short circuit or wire
break.
u
Check sensor B10 and wiring, replace as necessary
(→ Page 149).
211 – SD P-Lube Oil
Yellow alarm; power limitation < 20%;
Cause
Corrective action
Lube oil pressure sensor faulty;
short circuit or wire break.
u
Check sensor B5.1/5.3 and wiring, replace as necessary
(→ Page 149).
214 – SD P-Crankcase
Yellow alarm; warning
Cause
Corrective action
Crankcase pressure sensor
faulty; short circuit or wire
break.
u
Check sensor B50 and wiring, replace as necessary
(→ Page 149).
215 – SD P-HP Fuel
Yellow alarm; power limitation < 20%;
Cause
Corrective action
Rail pressure sensor faulty; high-
pressure regulator emergency
mode; short circuit or wire
break.
u
Check sensor B48 and wiring, replace as necessary
(→ Page 149).
216 – SD T-Lube Oil
Yellow alarm; warning
Cause
Corrective action
Lube oil temperature sensor
faulty; short circuit or wire
break.
u
Check sensor B7.1 and wiring, replace as necessary
(→ Page 149).
219 – SD T-Intake Air
Yellow alarm; warning
Cause
Corrective action
Intake air temperature sensor
faulty; short circuit or wire
break.
u
Check sensor B3 and wiring, replace as necessary
(→ Page 149).